6. Lead chiller temperature pulldown rate (TEMP PULL-
DOWN DEG/MIN on the TEMP_CTL screen) of the
chilled water temperature is less than 0.5 F (0.27 C) per
minute for a cumulative duration greater than the PULL-
DOWN TIMER setting in the LEAD/LAG screen.
When all the above requirements have been met, the lag
chiller is commanded to a STARTUP mode (indicated by
“CONTRL” flashing next to the CHILLER START/STOP pa-
rameter in the MAINSTAT screen). The PIC III control then
monitors the lag chiller for a successful start. If the lag chiller
fails to start, the standby chiller, if configured, is started.
Lead/Lag Pulldown Timer Operation
— Some lead/lag chill-
er applications with large chilled liquid loop volumes must ac-
commodate intermittent slugs of warm ENTERING
CHILLED WATER for short time periods. This type of tran-
sient condition can result when a control valve rapidly opens to
allow flow through a previously isolated branch or zone within
the chilled liquid system. A PULLDOWN TIMER can be con-
figured to delay starting the lag chiller so it does not excessive-
ly cycle on and off for short time periods when intermittent
slugs of warm ENTERING CHILLED WATER pass through
the chillers. A larger PULLDOWN TIMER entry gives the
warm slug of water more time to pass through the chillers be-
fore the lag chiller can start.
The chiller CONTROL POINT can be configured to either
LEAVING CHILLED WATER or ENTERING CHILLED
WATER temperature. The PIC controls monitor the tempera-
ture pulldown rate of the CHILLED WATER and display the
result as CHILL WATER PULLDOWN/MIN in the
HEAT_EX screen. Samples of the CHILLED WATER temper-
ature are taken once every 10 seconds and compared against
the previous CHILLED WATER sample. A positive value of
CHILL WATER PULLDOWN/MIN indicates that the
CHILLED WATER temperature is decreasing between succes-
sive samples. If CHILL WATER PULLDOWN/MIN rate is a
minimum of 0.5 degrees F per minute then the PULLDOWN:
SATISFIED parameter in the LL_MAINT screen displays
YES, otherwise, the PULLDOWN: SATISFIED parameter
displays NO.
If the lead chiller is unable to achieve the CONTROL
POINT, the lag chiller will not start unless the lead chiller is un-
able to maintain a CHILL WATER PULLDOWN/MIN rate of
0.5 degrees F per minute for a time period equal to the number
of minutes entered in the PULLDOWN TIMER parameter.
PULLDOWN TIME in the LL_MAINT screen displays the re-
maining delay left before the lag chiller is allowed to start
based on the pulldown timer. PULLDOWN TIME will count
down starting at the value entered in PULLDOWN TIMER
under the following conditions:
Ramp Loading is Complete
AND
PULLDOWN: SATISFIED = NO
The lag chiller pulldown start condition is met when PULL-
DOWN TIME lapses to 0.0 min.
If PULLDOWN: SATISFIED changes to YES as the
PULLDOWN TIME is counting down to zero, the PULL-
DOWN TIME will start to count back up provided that the
CHILLED WATER temperature has not fallen to less than the
CONTROL POINT plus one half of the CHILLED WATER
DEADBAND. The PULLDOWN TIME will start to count
back down again should PULLDOWN: SATISFIED change
back to NO. The PULLDOWN TIME will be immediately re-
set to the value entered in the PULLDOWN TIMER parameter
if the CHILLED WATER temperature decreases to less than
the CONTROL POINT plus one half of the CHILLED WA-
TER DEADBAND.
Lag Chiller Shutdown Requirements
— The following condi-
tions must be met in order for the lag chiller to be stopped.
1. Lead chiller AVERAGE LINE CURRENT or MOTOR
PERCENT KILOWATTS (on the MAINSTAT screen) is
less than the lead chiller percent capacity.
NOTE: Lead Chiller Percent Capacity = 115 – LAG %
CAPACITY. The LAG % CAPACITY parameter is on the
LEADLAG screen, which is accessed from the EQUIP-
MENT SERVICE table on the SERVICE menu.
2. The lead chiller chilled water temperature is less than the
CONTROL POINT temperature (see the MAINSTAT
screen) plus
1
/
2
the CHILLED WATER DEADBAND
temperature (see the SETUP1 screen).
3. The configured LAG STOP TIMER entry has elapsed.
The LAG STOP TIMER starts when the lead chiller
chilled water temperature is less than the chilled water
CONTROL POINT plus 1/2 of the CHILLED WATER
DEADBAND and the lead chiller compressor motor load
(MOTOR PERCENT KILOWATT or AVERAGE LINE
CURRENT on the MAINSTAT screen) is less than the
Lead Chiller Percent Capacity.
NOTE: Lead Chiller Percent Capacity = 115 – LAG %
CAPACITY. The LAG % CAPACITY parameter is on the
LEADLAG screen, which is accessed from the EQUIPMENT
SERVICE table on the SERVICE menu.
FAULTED CHILLER OPERATION — If the lead chiller
shuts down because of an alarm (*) condition, it stops commu-
nicating to the lag and standby chillers. After 30 seconds, the
lag chiller becomes the acting lead chiller and starts and stops
the standby chiller, if necessary.
If the lag chiller goes into alarm when the lead chiller is also
in alarm, the standby chiller reverts to a stand-alone CCN
mode of operation.
If the lead chiller is in an alarm (*) condition (as shown on
the ICVC panel), press the softkey to clear the alarm.
The chiller is placed in CCN mode. The lead chiller communi-
cates and monitors the RUN STATUS of the lag and standby
chillers. If both the lag and standby chillers are running, the
lead chiller does not attempt to start and does not assume the
role of lead chiller until either the lag or standby chiller shuts
down. If only one chiller is running, the lead chiller waits for a
start request from the operating chiller. When the configured
lead chiller starts, it assumes its role as lead chiller.
If the lag chiller is the only chiller running when the lead
chiller assumes its role as a lead chiller then the lag chiller will
perform a RECOVERY START REQUEST (LL_MAINT
screen). The lead chiller will start up when the following condi-
tions are met.
1. Lag chiller ramp loading must be complete.
2. Lag CHILLED WATER TEMP (MAINSTAT screen) is
greater than CONTROL POINT plus
1
/
2
the CHILLED
WATER DEADBAND temperature.
3. Lag chiller ACTIVE DEMAND LIMIT value must be
greater than 95% of full load amps.
4. Lag chiller temperature pulldown rate (TEMP PULL-
DOWN DEG/MIN) of the chilled water temperature is
less than 0.5 F (0.27 C) per minute.
5. The standby chiller is not running as a lag chiller.
6. The configured LAG START TIMER configured in the lag
(acting lead) chiller has elapsed. The LAG START TIMER
is started when the lag (acting lead) chiller’s ramp loading
is completed.
LOAD BALANCING — When the LOAD BALANCE OP-
TION (see LEADLAG screen) is enabled, the lead chiller sets
the ACTIVE DEMAND LIMIT in the lag chiller to the lead
chillers compressor motor load value MOTOR PERCENT
KILOWATTS or AVERAGE LINE CURRENT on the
RESET