Carrier XRV Specifikace Strana 1

Procházejte online nebo si stáhněte Specifikace pro ne Carrier XRV. Carrier XRV Specifications Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 190
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190015-01 Printed in U.S.A. Form 19XRV-5SS Pg 1 312 12-11 Replaces: 19XRV-2SS
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design speci-
fications. When operating this equipment, use good
judgment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures
and safety precautions contained in the chiller instruc-
tions as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accor-
dance with the latest edition of ANSI/ASHRAE 15 (American
National Standards Institute/American Society of Heating, Refrigerat-
ing, and Air Conditioning Engineers). The accumulation of refrigerant
in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE
15, especially for enclosed and low overhead spaces. Inhalation of
high concentrations of vapor is harmful and may cause heart irregular-
ities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design pres-
sures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
THERE IS A RISK OF INJURY OR DEATH by electrocution. High
voltage may be present on the motor leads even though the motor is
not running. Open the power supply disconnect before touching
motor leads or terminal
s.
D
O NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and the
work area should be well ventilated. Refrigerant in contact with an
open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control
panels, switches, VFD, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-state
components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY
FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar and
unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause
damage or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply with ANSI/ASHRAE 15 (latest edition).
Contact Carrier for further information on use of this chiller with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
chiller is under pressure or while chiller is running. Be sure pressure is
at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the
device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift
or move inspection covers or other heavy components. Even if
components are light, use mechanical equipment when there is a risk
of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE VFD, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the VFD, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements
of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for
corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or
rain water.
DANGER
WARNING
CAUTION
EVERGREEN
®
19XRV
Hermetic Centrifugal Liquid Chillers
with PIC III Controls and HFC-134a
50/60 Hz
Zobrazit stránku 0
1 2 3 4 5 6 ... 189 190

Shrnutí obsahu

Strany 1 - 50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Strany 2 - CONTENTS

10STARTING EQUIPMENTAll 19XRV units are equipped with a VFD to operate thecentrifugal hermetic compressor motor. A power panel controlsthe oil pump, a

Strany 3 - CONTENTS (cont)

100Table 16 — Alarm and Alert Messages (cont)J. CHILLER ALERTS (cont)*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set po

Strany 4 - INTRODUCTION

101Table 17 — Fault Code Descriptions and Corrective ActionsFault Type indicates if the fault is:1 — Auto-resettable2 — Non-resettable3 — User-configu

Strany 5 - (Fig. 1 and 2)

102Table 17 — Fault Code Descriptions and Corrective Actions (cont)Fault Type indicates if the fault is:1 — Auto-resettable2 — Non-resettable3 — User-

Strany 6

103Table 17 — Fault Code Descriptions and Corrective Actions (cont)Fault Type indicates if the fault is:1 — Auto-resettable2 — Non-resettable3 — User-

Strany 7 - FRONT VIEW

104Table 17 — Fault Code Descriptions and Corrective Actions (cont)Fault Type indicates if the fault is:1 — Auto-resettable2 — Non-resettable3 — User-

Strany 8 - COOLING CYCLE

105Table 18A — Thermistor Temperature (F) vs. Resistance/Voltage DropTEMPERATURE(F)PIC IIIVOLTAGEDROP (V)RESISTANCE(Ohms)–25 4.700 97,706–24 4.690 94,

Strany 9

106Table 18B — Thermistor Temperature (C) vs. Resistance/Voltage DropTEMPERATURE(C)PIC IIIVOLTAGEDROP (V)RESISTANCE(Ohms)–33 4.722 105 616–32 4.706

Strany 10 - STARTING EQUIPMENT

107Control ModulesThe ICVC and CCM modules perform continuous diagnos-tic evaluations of the hardware to determine its condition. Proper operation of

Strany 11 - OPTIONAL

108Replacing Defective Processor Modules — The module replacement part number is printed on a small label on the rear of the ICVC module. The chiller

Strany 12 - 900A AND 1200A VFDs

109release the force on SERVICE ONTIME after the desired value has been set.9. Perform the guide vane calibration procedure (in Control Test). Check a

Strany 13

11OPTIONAL METERPACKAGEFig. 5 — LF2 Variable Frequency Drive (VFD) External442A AND 608A VFDs900A AND 1200A VFDsa19-1718a19-1725

Strany 14

110DRIVE STATUS INDICATOR — The DRIVE status indica-tor is on the right side of the Gateway. See Table 19.Table 19 — DRIVE Status IndicatorMS STATUS I

Strany 15 - Definitions

111 Table 23A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water*Rigging weights are for standard tubes of standard wall thickness (0.02

Strany 16

112Table 23A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water (cont)*Rigging weights are for standard tubes of standard wall thickness (0.

Strany 17 - Fig. 11 — Power Panel

113Table 23B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water*Rigging weights are for standard tubes of standard wall thickness (0.02

Strany 18

114Table 23B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water (cont)*Rigging weights are for standard tubes of standard wall thicknes

Strany 19

115Table 24 — 19XRV Additional Data for Marine Waterboxes**Add to heat exchanger data for total weights or volumes.NOTE: For the total weight of a ves

Strany 20 - 21.8 132.9 93

116 Table 26A — 19XRV Compressor and Motor Weights* — Compressor Frame Size 2†*Total compressor weight is the sum of the compressor aerodynamic compon

Strany 21

117 Table 26B — 19XRV Compressor and Motor Weights* — Compressor Frame Size 3† (cont)*Total compressor weight is the sum of the compressor aerodynamic

Strany 22

118 Table 26B — 19XRV Compressor and Motor Weights* — Compressor Frame Size 3† (cont)*Total compressor weight is the sum of the compressor aerodynamic

Strany 23

119 Table 26C — 19XRV Compressor and Motor Weights* — Compressor Frame Size 4†*Total compressor weight is the sum of the compressor aerodynamic compon

Strany 24

124125368711, 117131618191, 214, 15, 19, 103456 9111012, 13, 715, 77, 814161712Fig. 6 — LF2 Variable Frequency Drive (VFD) Internal442A AND 608A VFDs9

Strany 25

120 Table 26C — 19XRV Compressor and Motor Weights* — Compressor Frame Size 4† (cont)*Total compressor weight is the sum of the compressor aerodynamic

Strany 26

121 Table 26D — 19XRV Compressor and Motor Weights* — Compressor Frame Size 5† (cont)*Total compressor weight is the sum of the compressor aerodynamic

Strany 27 - Table 4 — ICVC Display Data

122 Table 26D — 19XRV Compressor and Motor Weights* — Compressor Frame Size 5† (cont)*Total compressor weight is the sum of the compressor aerodynamic

Strany 28 - 0.1-3.0 SP_HIGH

123Table 27A — 19XRV Waterbox Cover Weights — English (lb) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in th

Strany 29

124Table 27A — 19XRV Waterbox Cover Weights — English (lb) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in the

Strany 30

125Table 27A — 19XRV Waterbox Cover Weights — English (lb) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in

Strany 31

126Table 27B — 19XRV Waterbox Cover Weights — SI (kg) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the hea

Strany 32

127Table 27B — 19XR Waterbox Cover Weights — SI (kg) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in t

Strany 33

128Table 27B — 19XR Waterbox Cover Weights — SI (kg) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the heat ex

Strany 34

129Table 28 — 19XRV Component Weights*To determine compressor frame size, refer to 19XR,XRV Computer Selection Program.†Included in total cooler weigh

Strany 35

132512431514131181412108371161095678222019211816172324202526*The inverter control assembly (item 16) and rectifier control assembly (item 18) are phys

Strany 36

13019XRV COMPRESSOR FITS AND CLEARANCES (in.)*Depends on impeller size, contact your Carrier Service Represen-tative for more information.NOTES:1. Al

Strany 37 - 0.1-3.0 SP_HIGH 1.0

131C1BTHRUSTTHRUSTC1C2BVIEW A1LOW SPEED SHAFT THRUST DISKVIEW A2LOW SPEED SHAFT THRUST DISKa19-1636a19-1637POF1HEF2KIJIMPELLER SHIMMINGTO BE DETERMINE

Strany 38

132+0.0007-0.00070.00110.0013THRUST0.0250.005INTERFERENCE0.00110.0013INTERFERENCE+0.0007-0.00070.00500.00200.00120.0004NMVIEW B — HIGH SPEED SHAFT (FR

Strany 39

133LEGEND FOR FIG. 53-58MOTOR LEAD INSTALLATION LABELS19XRV COMPRESSOR ASSEMBLY TORQUESFig. 52 — Compressor Fits and Clearances (cont)ITEMCOMPRESSOR F

Strany 40 - PIC III System Functions

134NOISESUPPRESSORVFD COOLANTSOLENOID)RLC()KLB()NRB((BRN)RMS+S-RELATIVEHUMIDITY(BLK)(WHT)(RED)JUMPERJUMPERRSTOPICVCALARMJ7J1J85424VAC32G+-1(RED)(GRY)(

Strany 41 - Error, Gain = 3

135Fig. 53 — Typical Electronic PIC III Control Panel Wiring Schematic (cont)(RED)(BLK)(BRN) (BRN)(WHT)T224VAC(GRN)(RED)(RED)(BLU)(BLU)(BLK)SOLENOIDHG

Strany 42

136TO VFD(RED)(CLR)TO CCM J7-1*(RED)TO CCM J7-3*(BLK)TO CCM J7-2*(BLK)(BLK)(BLK)COMPR DISCHHIGH PRESSTO CCM J1-2*TO CB1*(RED) (GRY)SOLENOIDVFD COOLANT

Strany 43

137Fig. 55 — 19XRV 442A and 608A Chiller Control Schematica19-1733

Strany 44

138UPC12Fig. 55 — 19XRV 442A and 608A Chiller Control Schematic (cont)a19-1997

Strany 45

139Fig. 55 — 19XRV 442A and 608A Chiller Control Schematic (cont)a19-2015312

Strany 46

1411817163151413646X322X5UNDER TOP COVER7891011122XFig. 7 — LF2 Power Module Components (cont)Door OpenDoor Closeda19-1728a19-1729900A AND 1200A VFDs1

Strany 47

140Fig. 56 — 19XRV 900A and 1200A Chiller Control Schematica19-1736

Strany 48

141UPC12Fig. 56 — 19XRV 900A and 1200A Chiller Control Schematic (cont)a19-1999

Strany 49

142Fig. 56 — 19XRV 900A and 1200A Chiller Control Schematic (cont)a19-2016312

Strany 50

143Fig. 57 — 19XRV 442A and 608A Chiller VFD Schematic120V_N120VSWITCHEDMETERS W/SWITCH(OPTIONAL)VOLTMETERVM1RELAYP1-9P1-12A2 LINE SYNC PCBP1-14P1-7

Strany 51

144206 208207L2T2A1A2L3T3L1T11314225F231G13A1CONTACTORSPRECHARGEK1AT2L2A2T3L3K1BT1L114231H225CK1CT2L2A1L3A2T3L113T114L2L1L3VFD POWER MODULECOMBINED I/

Strany 52

145Fig. 59 — 19XRV Chiller Control Panel Component Layouta19-2001

Strany 53

146 TB1 − LF2VFD FRAME 3 TB3 − LF2VFD FRAME 4 TB1 − LF2VFD FRAME 4GATE KILL OIL PUMPINTERLOCKPOWERPAN EL OIL PUMPINTERLOCK TB2*†***Fig. 60 — 19XRV

Strany 54

147Fig. 60 — 19XRV Field Wiring — LiquiFlowTM VFD (cont)a19-1714

Strany 55

148LEGEND FOR FIG. 60REFERENCENUMBERDESCRIPTION13 Phase Under/Over Voltage Protection (Line Side)Phase Loss/Imbalance/Reversal Protection (Line Side)F

Strany 56

149NOTES FOR FIG. 60I General1.0 Variable Frequency Drive (VFD) shall be designed and manu-factured in accordance with Carrier engineering requirement

Strany 57 - Local Start-Up —

15CONTROLSDefinitionsANALOG SIGNAL — An analog signal varies in proportionto the monitored source. It quantifies values between operatinglimits. (Exam

Strany 58

150 OIL PUMPINTERLOCK OIL PUMPINTERLOCKPOWERPAN ELTB4-1SEENOTE 3.6 Fig. 61 — 19XRV Field Wiring — Standard Tier VFDa19-1950

Strany 59

151Fig. 61 — 19XRV Field Wiring — Standard Tier VFD (cont)a19-1951

Strany 60 - Shaft Packing —

152LEGEND FOR FIG. 61REFERENCENUMBEREXPLANATION13 Phase Under/Over Voltage (Line Side)Phase Loss/Imbalance/Reversal (Line Side)Frequency Shift Protect

Strany 61

153NOTES FOR FIG. 61I General1.0 Variable Frequency Drive (VFD) shall be designed and manu-factured in accordance with Carrier engineering requirement

Strany 62

15423423412345REDBLKWHT1515REDBLKWHTREDBLKWHT19XRV CHILLERS LEGENDNOTE: Field supplied terminal strip must be located in control panel.Fig. 62 —

Strany 63 - LIQUID LINE

155APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEXPARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLE0% Actual Guide Vane Position SERVICE CONTROL

Strany 64 - Temperature (C)

156APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEChilled Water Delta T STATUS HEAT_EX

Strany 65

157APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLECondenser Water Delta P SERVICE CONTRO

Strany 66

158APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEEntering Chilled Water SERVICE CONTROL

Strany 67

159APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEICVC CONFIGURATION SERVICE IGV &a

Strany 68

16INTERNATIONAL CHILLER VISUAL CONTROLLER(ICVC) — The ICVC is the “brain” of the PIC III system. Thismodule contains all the operating software needed

Strany 69 - • Surge/ HGBP Deadband = 1

160APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLELine Volt Imbalance Time SERVICE VFD C

Strany 70 - ΔT increase

161APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEOil Pressure DEFAULT SCREEN Oil P

Strany 71 - Delta Tsat

162APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLERemote Reset Option STATUS ICVC_PWD

Strany 72 - ALARM ROUTING

163APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEStop Fault STATUS VFD_STAT Stop Mon

Strany 73

164APPENDIX A — 19XRV LIQUIFLO™ 2 ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLETower Fan Relay High Test SERVICE CONT

Strany 74

165APPENDIX B — LEAD/LAG WIRING 19XR Lead Lag Schematic Series Cooler Flowa19-1655

Strany 75

166APPENDIX B — LEAD/LAG WIRING (cont)19XR Lead Lag Schematic Parallel Cooler Flowa19-1717

Strany 76

167APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XRV Maintenance Interval RequirementsNOTE: Equipment failures caused by lack of adherence to the M

Strany 77

168APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XRV Weekly Maintenance LogPlant ___________________________Machine Serial No. ___________________

Strany 78

169APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XRV Maintenance LogNOTE: Equipment failures caused by lack of adherence to the Maintenance Interva

Strany 79

17CONTROLPANELSIDE VIEWREMOVABLEBOLTHINGECHILLER IDENTIFICATION NAMEPLATEOIL HEATER CONDUITCONTROL PANELPOWER CONDUITOPTIONAL HOT GASBYPASS CONDUIT3C

Strany 80

170APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XRV Seasonal Shutdown LogNOTE: Equipment failures caused by lack of adherence to the Maintenance I

Strany 81

171APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRINGOptional BACnet* Communications Wiring — The following section is used to configure the UPC Open

Strany 82

172APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)CONFIGURING THE BAS PORT FOR BACNET MS/TP — Use the same baud rate and communication setti

Strany 83

173APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)To install a BT485 terminator, push the BT485 terminator on to the BT485 connector located

Strany 84

174APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table D — Open System Wiring Specifications and Recommended Vendors LEGENDLO

Strany 85

175APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)COMMUNICATION LEDS — The LEDs indicate if the controller is communicating with the device

Strany 86

176APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table G — Network Points List LEGENDPOINT DESCRIPTIONCCNPOINT NAMEREAD/WRITEUNI

Strany 87

177APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table G — Network Points List (cont) LEGENDPOINT DESCRIPTIONCCNPOINT NAMEREAD/W

Strany 88

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Strany 89

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Strany 90

18CONTROL TRANSFORMERS (T1, T2) — These transform-ers convert incoming control voltage to 24 vac power for the3 power panel contactor relays, CCM, and

Strany 91 - LEGEND TO TABLES 16A-16J

CL-2- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 92 - E. START-UP IN PROGRESS

CL-319XRV PIC III SETPOINT TABLE CONFIGURATION SHEETUpload all control configuration tables via service tool? Ye s  No ICV

Strany 93 - G. NORMAL RUN WITH OVERRIDES

CL-4- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 94 - H. OUT-OF-RANGE SENSOR

CL-519XRV PIC III VFD_CONF TABLE CONFIGURATION SHEETNOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in ot

Strany 95

CL-6- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 96

CL-719XRV PIC III SETUP1 TABLE CONFIGURATION SHEETNOTE: No variables are available for CCN read operation. Forcing shall not be supported on service s

Strany 97

CL-8- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 98

CL-919XRV PIC III LEADLAG TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VA L U ELead Lag Control LEAD/LAG: ConfigurationDSABLE=0,

Strany 99 - J. CHILLER ALERTS

CL-10- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 100 - J. CHILLER ALERTS (cont)

CL-11BROADCAST (BRODEF) CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VA L U ETime Broadcast Enable DSABLE/ENABLE DSABLEDaylight Savings

Strany 101

19A Refrigerant Saturation Temperature sensor (thermistor) islocated in the base of the evaporator, sensing refrigeranttemperature directly. Evaporato

Strany 102

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Strany 103

2CONTENTSPageSAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 104

20When an alarm is detected, the ICVC default screen willfreeze (stop updating) at the time of alarm. The freeze enablesthe operator to view the chill

Strany 105

21CCN LOCAL RESET MENU DEF AUL T SCREEN Start Chiller In CCN Control Start Chiller in Local Control Clear Alarm s ST AT U S SCHEDULE SETPOINT SER V

Strany 106

22NEXT PREVIOUS SELECT EXI T SER VICE T ABLE Display Alarm History (The table holds up to 25 alarms with the most recent alarm at the top of the sc

Strany 107 - Notes on Module Operation

23NEXTPREVIOUSSELECTEXITSERVICE MENU CONTINUEDFROM PREVIOUS PAGESelect a Service TableSelect a Service Table ParameterNEXTPREVIOUSSELECTEXITModify a S

Strany 108

24TO VIEW STATUS (Fig. 18) — The status table shows theactual value of overall chiller status such as CONTROLMODE, RUN STATUS, AUTO CHILLED WATER

Strany 109 - INVERTER LED

25Force Indication — A forced value is indicated by“SUPVSR,” “SERVC,” or “BEST” flashing next to the pointvalue on the STATUS table.TIME SCHEDULE OPER

Strany 110

262. There are 5 set points on this screen: BASE DEMANDLIMIT, LCW SETPOINT (leaving chilled water setpoint), ECW SETPOINT (entering chilled water setp

Strany 111

27Table 4 — ICVC Display Data1. Only 12 lines of information appear on the chiller display screenat any one time. Press the or softkey tohighlight

Strany 112

28Table 4 — ICVC Display Data (cont)EXAMPLE 2 — MAINTSTAT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press ( wi

Strany 113

29Table 4 — ICVC Display Data (cont)EXAMPLE 4 — STARTUP DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Strany 114

3CONTENTS (cont)PageStanding Vacuum Test . . . . . . . . . . . . . . . . . . . . . . . . . . 62Chiller Dehydration . . . . . . . . . . . . . . . . .

Strany 115

30Table 4 — ICVC Display Data (cont)EXAMPLE 6 — HEAT_EX DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Strany 116

31Table 4 — ICVC Display Data (cont)EXAMPLE 7 — POWER DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scroll

Strany 117

32Table 4 — ICVC Display Data (cont)EXAMPLE 8 — VFD_STAT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Strany 118

33Table 4 — ICVC Display Data (cont)EXAMPLE 11 — CAPACITY DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scr

Strany 119

34Table 4 — ICVC Display Data (cont)EXAMPLE 13 — SURGPREV DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scr

Strany 120

35Table 4 — ICVC Display Data (cont)EXAMPLE 15 — VFD_HIST DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scr

Strany 121

36Table 4 — ICVC Display Data (cont)EXAMPLE 17 — NET_OPT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Strany 122

37Table 4 — ICVC Display Data (cont)EXAMPLE 19 — OPTIONS DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Strany 123

38Table 4 — ICVC Display Data (cont)EXAMPLE 20 — SETUP1 DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Strany 124

39Table 4 — ICVC Display Data (cont)EXAMPLE 22 — LEADLAG DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Strany 125

4CONTENTS (cont)PageOptional Pumpout System Maintenance . . . . . . . . . 88• OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE• OPTIONAL PUMPOUT SAFETY CONTROLS

Strany 126

40PIC III System FunctionsCAPACITY CONTROL — Generally the chiller adjusts ca-pacity in response to deviation of leaving or entering chilledwater temp

Strany 127

41When very close temperature control is required, as forsome process applications, the deadband may be reduced.When constant small load changes occur

Strany 128

42DIFFUSER CONTROL — On all units with Frame 5 com-pressors and those Frame 4 compressors with the variable (splitring) diffuser option, the PIC III a

Strany 129 - Table 30 — Motor Voltage Code

43These schedules can be set up to follow a building’soccupancy schedule, or the chiller can be set so to run 100% ofthe time, if the operator wishes.

Strany 130 - COMPRESSOR, TRANSMISSION AREA

44Table 6 — Protective Safety Limits and Control SettingsMONITORED PARAMETERALARM/ALERTLIMIT COMMENTSTemperature Sensors Out of Range260-271,140,141.0

Strany 131 - LOW SPEED SHAFT THRUST DISK

45Table 6 — Protective Limits and Control Settings (cont)MONITORED PARAMETER ALARM/ALERT LIMIT COMMENTSMotor — Surge 238> 5 surge events within SUR

Strany 132

46Ramp Loading — The ramp loading control slows downthe rate at which the compressor loads up. This control can pre-vent the compressor from loading u

Strany 133 - LEGEND FOR FIG. 53-58

47valves are strapped to the oil supply line leaving the heatexchanger, and the valves are set to maintain 110 F (43 C).NOTE: The TXVs are not adjusta

Strany 134 - SEE NOTE

48Kilowatt Output — An output is available on the CCMmodule [Terminal J8-1 (+) and J8-2 (–)] to represent the powerconsumption of the chiller. The 4 t

Strany 135 - HOT GAS BYPASS

49The TOWER FAN RELAY LOW and TOWER FAN RELAYHIGH parameters are accessed from the STARTUP screen. Auto. Restart After Power Failure — This optionmay

Strany 136 - HOT GAS BYPASS OPTION FOR

5Factory-installed additional components are referred to asoptions in this manual; factory-supplied but field-installedadditional components are refer

Strany 137

50quire a measurement of COOLER DELTA T and is thus unaf-fected by changes in flow. With Variable Primary Flow SurgePrevention there is no difference

Strany 138

51by the amount configured in the VFD INCREASE STEP pa-rameter. The VFD will not decrease in speed if SURGECOUNTS is greater than zero. The threshold

Strany 139

52If the entering chilled water control option (ECW CON-TROL OPTION) is enabled (configured in TEMP_CTLscreen) and a common point sensor is desired (C

Strany 140

536. Lead chiller temperature pulldown rate (TEMP PULL-DOWN DEG/MIN on the TEMP_CTL screen) of thechilled water temperature is less than 0.5 F (0.27

Strany 141

54MAINSTAT screen). This value has limits of 40% to 100%. Inaddition, the CONTROL POINT for the lag chiller must bemodified to a value of 3 F (1.67 C)

Strany 142

55TERMINATION OF ICE BUILD — The ice build functionterminates under the following conditions:1. Time Schedule — When the current time on the ice bu

Strany 143 - DO NOT ADJUST

56Service Operation — An overview of the tables andscreens available for the SERVICE function is shown inFig. 17.TO ACCESS THE SERVICE SCREENS — When

Strany 144 - COMBINED I/O

577. Press to access the holiday table. The Config-uration Select table now shows the holiday start monthand day, and how many days the holiday peri

Strany 145

58NOTE: The 19XRV units are not available with factory-installed chilled water or condenser water flow devices (avail-able as an accessory for use wit

Strany 146 - TB3 − LF2

59Table 9 — Prestart ChecksChilled Water Recycle Mode — The chiller maycycle off and wait until the load increases to restart when thecompressor is ru

Strany 147 - VFD (cont)

6System Components — The components include thecooler and condenser heat exchangers in separate vessels,compressor-motor, lubrication package, control

Strany 148 - LEGEND FOR FIG. 60

60Oil Charge — The oil charge for the 19XRV compressordepends on the compressor Frame size:• Frame 2 compressor — 8 gal (30 L)• Frame 3 compressor —

Strany 149 - NOTES FOR FIG. 60

61Fig. 29 — 19XRV Leak Test Proceduresa19-1625

Strany 150 - NOTE 3.6

62If the chiller is spring isolated, keep all springs blocked inboth directions to prevent possible piping stress and damageduring the transfer of ref

Strany 151

63STORAGETANK LIQUIDVALVEOILSEPARATORPUMPOUTCONDENSERWATER SUPPLYAND RETURNPUMPOUTCONDENSERSTORAGE TANKVAPOR VA LVE2345PRESSURERELIEF SAFETY VALVEPUMP

Strany 152 - LEGEND FOR FIG. 61

64Table 11A — HFC-134a Pressure —Temperature (F)Table 11B — HFC-134a Pressure —Temperature (C)TEMPERATURE,FPRESSURE(psig)0 6.502 7.524 8.606 9.668 10.

Strany 153 - NOTES FOR FIG. 61

65Chiller Dehydration — Dehydration is recommended ifthe chiller has been open for a considerable period of time, ifthe chiller is known to contain mo

Strany 154 - 19XRV CHILLERS

66IDENTIFYING THE DRIVE BY PART NUMBER — EachAC drive can be identified by its assembly number. SeeFig. 33. This number appears on the shipping label

Strany 155

67Inspect Wiring 1. Examine the wiring for conformance to the job wiringdiagrams and all applicable electrical codes.2. Connect a voltmeter across the

Strany 156

68SOFTWARE VERSION — The software part number islabeled on the backside of the ICVC module. The softwareversion also appears on the ICVC configura

Strany 157

69VERIFY VFD CONFIGURATION AND CHANGEPARAMETERS IF NECESSARY (Fig. 35)VFD CHILLER FIELD SET UP AND VERIFICATIONLabel Locations — Verify that the follo

Strany 158

719181716151314134576891110122282627262529303132333435362021222324Fig. 2 — Typical 19XRV Components LEGEND1—Guide Van

Strany 159

70Maximum Load T2:54 – 44 = 10º F (12.2 – 6.7 = 5.5º C)Maximum Load P2:120 – 37 = 83 psid (827 – 255 = 572 kPad)To avoid unnecessary surge preventio

Strany 160

71Fine Tuning VPF Surge Prevention — Figures 36-39 showhow the parameters defined below will affect the configuredsurge line.NOTE: Before tuning surge

Strany 161

72failed (with ACTUAL GUIDE VANE POSITION great-er than 60), then perform this step. Do not changeSURGE LINE SHAPE FACTOR from the value speci-fied by

Strany 162

73Table 13 — Control Test Menu Functions*Diffuser tests function only on size 4 and 5 compressor with diffusercontrol enabled.NOTE: During any of the

Strany 163 - STATUS VPF_STAT

74If the ICVC fails to accept the high end calibration, thevalue will not change and the display will show “Higher ForceIn Effect.” This indicates tha

Strany 164

75Table 14A — Refrigerant (HFC-134a) Charge with Compressor End Entering Cooler WaterCODEMACHINE CHARGEEnglish Metric (SI)RefrigerantWeight (lb)Refrig

Strany 165 - APPENDIX B — LEAD/LAG WIRING

76Table 14B — Refrigerant (HFC-134a) Charge with Drive End Entering Cooler WaterCODEMACHINE CHARGEEnglish Metric (SI)RefrigerantWeight (lb)Refrigerant

Strany 166

77Use the CONTROL TEST terminate lockout function tomonitor conditions and start the pumps.If the chiller has been shipped with a holding charge, ther

Strany 167

78Check Oil Pressure and Compressor Stop1. When the motor is at full speed, note the OIL PRES-SURE reading on the ICVC default screen. Normal19XRV oil

Strany 168 - 19XRV Weekly Maintenance Log

79be up to 10 psid (69 kPad) higher for Frame 3 compres-sors equipped with rolling element bearings.5. The moisture indicator sight glass on the refri

Strany 169 - 19XRV Maintenance Log

8REFRIGERATION CYCLEThe compressor continuously draws refrigerant vapor fromthe cooler at a rate set by the amount of guide vane opening orcompressor

Strany 170 - 19XRV Seasonal Shutdown Log

80REFRIGERATION LOG CARRIER 19XRV HERMETIC CENTRIFUGAL REFRIGERATION MACHINEPlant MODEL NO. SERIAL NO. MOTOR RLA Fig. 42 — Refrigeration LogDATECOOL

Strany 171 - 1's

81PUMPOUT AND REFRIGERANTTRANSFER PROCEDURESPreparation — The 19XRV chiller may come equippedwith an optional pumpout storage tank, pumpout system, or

Strany 172

82Transfer Refrigerant from Pumpout Storage Tank to Chiller1. Equalize refrigerant pressure.a. Turn on chiller water pumps and monitor chillerpressure

Strany 173

834. Establish vacuum for service. To conserve refrigerant,operate the pumpout compressor as described in Step 3euntil the chiller pressure is reduced

Strany 174

84b. Close pumpout and storage tank valves 2, 4, 5, and10, and close chiller charging valve 7; open chillerisolation valve 11 and any other chiller is

Strany 175 - — The LEDs indicate if the

85Repair the Leak, Retest, and Apply StandingVacuum Test — After pressurizing the chiller, test forleaks with an electronic halide leak detector, soap

Strany 176 - Table G — Network Points List

86SCHEDULED MAINTENANCEEstablish a regular maintenance schedule based on actualchiller requirements such as chiller load, run hours, and waterquality.

Strany 177

87VFD Refrigerant Strainer — A refrigerant strainer islocated in the 5/8 in. line that supplies refrigerant to the VFD.The strainer should be replaced

Strany 178

88Water Treatment — Untreated or improperly treatedwater may result in corrosion, scaling, erosion, or algae. Theservices of a qualified water treatme

Strany 179 - INITIAL START-UP CHECKLIST

89TROUBLESHOOTING GUIDE (Tables 15-18B)Overview — The PIC III has many features to help theoperator and technician troubleshoot a 19XRV chiller.• The

Strany 180 - DRAWINGS)

9VFD COOLING CYCLEThe unit-mounted variable frequency drive (VFD) is cooledin a manner similar to the motor and lubricating oil coolingcycle (Fig. 3).

Strany 181

90COOLER CONDENSER PRESSURE TRANSDUCERAND OPTIONAL WATERSIDE FLOW DEVICE CALI-BRATION — Calibration can be checked by comparing thepressure readings f

Strany 182

91Control Test — The Control Test feature can check all thethermistor temperature sensors, pressure transducers, pumpsand their associated flow device

Strany 183

92Table 16 — Alarm and Alert Messages (cont)D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue

Strany 184 - 0.1 to 3.0

93Table 16 — Alarm and Alert Messages (cont)F. NORMAL RUNG. NORMAL RUN WITH OVERRIDES*[LIMIT] is shown on the ICVC as the temperature, pressure, volta

Strany 185

94Table 16 — Alarm and Alert Messages (cont)H. OUT-OF-RANGE SENSORICVC FAULTSTATEPRIMARYMESSAGESECONDARYMESSAGEPRIMARY CAUSE ADDITIONAL CAUSE/REMEDY26

Strany 186

95Table 16 — Alarm and Alert Messages (cont)I. CHILLER PROTECTIVE LIMIT FAULTS*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc

Strany 187

96Table 16 — Alarm and Alert Messaged (cont)I. CHILLER PROTECTIVE LIMIT FAULTS (cont)*[LIMIT] is shown on the ICVC as the temperature, pressure, volta

Strany 188

97Table 16 — Alarm and Alert Messages (cont)I. CHILLER PROTECTIVE LIMIT FAULTS (cont)*[LIMIT] is shown on the ICVC as the temperature, pressure, volta

Strany 189

98Table 16 — Alarm and Alert Messages (cont)I. CHILLER PROTECTIVE LIMIT FAULTS (cont)*[LIMIT] is shown on the ICVC as the temperature, pressure, volta

Strany 190 - CCN LOCAL RESET MENU

99Table 16 — Alarm and Alert Messages (cont)I. CHILLER PROTECTIVE LIMIT FAULTS (cont)*[LIMIT] is shown on the ICVC as the temperature, pressure, volta

Komentáře k této Příručce

Žádné komentáře