R410A REFRIGERANT
OUTDOOR FAN M UST BE OPERATING ON HIGH SPEED
150 200 250 300 350 400 450 500 550 600
Compressor Discharge Pressure, [psig]
Fig. 30 -- Charging Chart -- 50PG07
PURON® REFRIGERANT -- Puron refrigerant operates at
50 to 70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are designed
to operate with Puron refrigerant. Do not mix with components
that have been used with other refrigerants. Puron refrigerant,
as with other HFCs, is only compatible with POE oils.
Recovery cylinder service pressure rating must be 400 psig.
Puron systems should be charged with liquid refrigerant. Use a
commercial-type metering device in the manifold hose. Mani-
fold sets should be 750 psig high-side and 200 psig low-side
with 520 psig low-side ret_ud. Use hoses with 750 psig service
pressure rating. Leak detectors should be designed to detect
HFC refrigerant.
Filter Drier -- Replace whenever refrigerant system is ex-
posed to atmosphere. Only use factory specified liquid-line
filter driers with working pressures no less than 650 psig. Do
not install a suction-line filter drier in liquid line. A liquid-line
filter drier designed for use with Puron refligemnt is required
on every unit.
Protective Devices
COMPRESSOR PROTECTION
High-Pressure Switch -- If the high-pressure switch opens, the
compressor will shut down. On 3-phase units, the compressor
lockout (CLO) device will energize to block lhrther compres-
sor operation. The high-pressure switch will reset automatical-
ly as the refrigerant pressure drops below its reset level. On
3-phase units, the CLO will remain energized until manually
reset.
Low-Pressure Switch -- If the low-pressure switch opens,
the compressor will shut down. On 3-phase units, the compres-
sor lockout (CLO) device will energize to block further com-
pressor operation. The low-pressure switch will reset automati-
cally as the refrigerant pressure rises above its reset level. On
3-phase units, the CLO will remtdn energized until manually
reset.
Freeze Protection Switch -- This switch is installed on each
evaporator coil section to provide protection against continued
unit operation with a frosted evaporator surface. If the freeze
protection switch opens, the compressor on this circuit will
shut down. On 3-phase units, tthe compressor lockout (CLO)
device will energize to block further compressor operation. The
freeze protection switch will reset as the evaporator tube tem-
perature rises above its reset level. On 3-phase units, the CLO
will remain energized until manually reset.
Compressor Ix)ckout (CLO) Device (3-Phase Units Only) --
The CLO prevents automatic recycling of the compressor as
safety controls reset. If the high-pressure switch, low-pressure
switch or freeze protection switch opens, the CLO device will
energize to block further compressor operation. To reset the
CLO (after all safety switches have reset), either open the ther-
mostat to remove the cooling demand signal (and then
re-close) or cycle the control power in the unit.
Overcurrent -- Each compressor has internal line break motor
protection.
Overtemperature -- Each compressor has an interned protector
to protect it agtdnst excessively high discharge gas temperatures.
EVAPORATOR FAN MOTOR PROTECTION -- Indoor fan
motors less than 5 hp are equipped with internal overcurrent
and overtemperature protection. Protection devices reset auto-
matically. Disconnect and lock out power when servicing
motol: Indoor-fan motors 5 hp and larger tue equipped with a
manual reset, calibrated trip, magnetic circuit breaker and over-
current protection. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
conect it before resetting the breakec
CONDENSER-FAN MOTOR PROTECTION -- Each
condenser-fan motor is intern_dly protected against
overtemperature.
Relief Devices -- All units have relief devices to protect
against &image from excessive pressures (i.e., fire). These
devices protect the high and low side and are located at the suc-
tion line service port. Protect joint during brazing operations
netu joint.
Control Circuit, 24-V- Each control circuit is pro-
tected against overcurrent by a 3.2 amp circuit breakel:
Breaker can be reset. [f it trips, determine cause of trouble
before resetting. See Fig. 31 and 32.
Replacement Parts -- A complete list of replacement
parts may be obt_dned from any Cartier distributor upon
request.
42
Zobrazit stránku 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 48 49

Komentáře k této Příručce

Žádné komentáře

Impulse R17ID7T-OFM1 manuels

Manuels d'utilisation et guides de l'utilisateur pour Ordinateurs Impulse R17ID7T-OFM1.
Nous fournissons des manuels en pdf 1 Impulse R17ID7T-OFM1 à télécharger gratuitement par type de document : Manuel de l'utilisateur


Impulse R17ID7T-OFM1 Manuel de l'utilisateur (1 pages)


marque: Impulse | Catégorie: Computers | Taille: 0.24 MB |

 

Table des matières





Plus de produits et de manuels pour Ordinateurs Impulse

Modèles Type de document
R17IC7T-OFM1 Manuel de l'utilisateur   Impulse R17IC7T-OFM1 User Manual [ru] , 1 pages
R15ID7T-OFC3 Manuel de l'utilisateur   Impulse R15ID7T-OFC3 User Manual, 1 pages
R15IC7T-OFC3 Manuel de l'utilisateur   Impulse R15IC7T-OFC3 User Manual, 1 pages
R15IC7T-OFA1 Manuel de l'utilisateur   Impulse R15IC7T-OFA1 User Manual, 1 pages
R10ID7T-OFP1 Manuel de l'utilisateur   Impulse R10ID7T-OFP1 User Manual, 1 pages
R12ID7T-OFL1 Manuel de l'utilisateur   Impulse R12ID7T-OFL1 User Manual, 1 pages
W10ID3S-OFH1 Manuel de l'utilisateur   Impulse W10ID3S-OFH1 User Manual, 1 pages
R08ID3S-OFT1 Manuel de l'utilisateur   Impulse R08ID3S-OFT1 User Manual, 1 pages
W22IC7T-PMA3 Manuel de l'utilisateur   Impulse W22IC7T-PMA3 User Manual [ru] , 1 pages
MPC-2240 Manuel de l'utilisateur   Impulse MPC-2240 User Manual, 3 pages
R20IC7T-PMA2 Manuel de l'utilisateur   Impulse R20IC7T-PMA2 User Manual, 1 pages
R19IC7T-PMM1 Manuel de l'utilisateur   Impulse R19IC7T-PMM1 User Manual, 1 pages
R17IC7T-PMM1 Manuel de l'utilisateur   Impulse R17IC7T-PMM1 User Manual, 1 pages
R15IC7T-PMA1 Manuel de l'utilisateur   Impulse R15IC7T-PMA1 User Manual, 1 pages
R15IC7T-PMC3 Manuel de l'utilisateur   Impulse R15IC7T-PMC3 User Manual, 1 pages
WebOP-2100T Manuel de l'utilisateur   Impulse WebOP-2100T User Manual [ru] , 2 pages
WebOP-2080T Manuel de l'utilisateur   Impulse WebOP-2080T User Manual, 2 pages
WebOP-2070T Manuel de l'utilisateur   Impulse WebOP-2070T User Manual [ru] , 2 pages
WebOP-2040T Manuel de l'utilisateur   Impulse WebOP-2040T User Manual, 2 pages
WebOP-2050T Manuel de l'utilisateur   Impulse WebOP-2050T User Manual, 2 pages