
Step 7-- Make Electrical Connections
FIELD POWER SUPPLY -- All 2081230-v units are factory
wired for 230-v power supply. If the 2081230-v unit is to be
connected to a 208-v power supply, the transformer must be m-
wired by moving the black wire with the l/4-in, female quick
connect from the 230-volt connection and moving to the
200-volt l/4-in, m_de temfinal on the prma U side of the
transfonnel:
Refer to unit label diagram for additional infonnaion.
All field wirng must comply with NEC (National Electrical
Code) and local codes. Size wire based on MCA (Minimum
Circuit Amps) on the unit informaive plae. Leads am provided
for field wire connections. Use UL (Underwrters' Laborato-
res) approved copper/aluminum connectol:
When installing units, provide safety disconnect per NEC
Article 440 or local codes. For non-lused disconnects, size the
disconnect according to the sizing data provided in the electri-
cal daa tables. If a fused disconnect is used, determine the
minimum size for the switch based on the disconnect sizing
data provided in the electrical data tables and then coordinate
the disconnect housing size to accommodate the Maximum
Overcurrent Protection (MOCP) device size as marked on the
unit informative plate. See Tables 2A and 2B.
See Fig. 8 for power wiring connection to unit leads and
equipment ground.
Route power and ground lines through control box end
panel or unit basepan (see Fig. 3) to connections as shown on
unit wiring diagram and Fig. 8. Make sure that there is a
watertight seal when penetrating the cabinet. Factory leads
may be wired directly to the disconnect.
The correct power phasing is critical to the operation of the
scroll compressors. An incorrect phasing will result in an
alarm being generated and compressor operation lockout.
Should this occur, power phase correction must be made to
the incoming powel: Damage to compressor could result.
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occm: This ground may consist of
electrcal wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC; ANSI/NFPA (American
National Standards Institute/Natiomd Fire Protection Asso-
ciation), latest edition, and local electric_d codes. Failure to
follow this wmning could result in the installer being liable
for personal injury of others.
Field wiring must conform to temperature limitations for
type "T" wire. All field wiring must comply with NEC and
local requirements.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
FIELD CONTROL WIRING -- Unit can be controlled with
a cmrer-approved accessoly thermostat. Inst_dlthermostat ac-
cording to the inst_dlation instructions included with accessory.
Ix_cate thermostat assembly on a solid interior wall in the
conditioned space to sense average temperature.
Route fllermostat cable or equivalent single leads of colored
wire from subbase terminals through conduit into unit to
low-voltage connections as shown on unit label wiring diagram
and in Fig. 9.
If bottom entU is used, seal the hole in the grommet of the
control box with RTV se_dant.
NOTE: For wire runs up to 50 It, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 It,
use no. 16 AWG insulated wire (35 C minimum). For over
75 It, use no. 14 AWG insulated wire (35 C Minimum). All
wire larger than no. 18 AWG cannot be directly connected at
the thermostatand will require a junction box and splice at the
thermostat.
Set heat anticipator settings as follows:
STAGE 1
VOLTAGE (Wl) ON
All 0.2
STAGE 1 AND 2
(Wl AND W2) ON
0.4
Settings may be changed slightly to provide a greater degree
of comfort for a particulm installation.
F--
Om
(DO-
FIELD ,=_ FACTORY
POWER ,__ POWER
WIRING WIRING
C.A1
EQUIP GND
LEGEND
C.A1 -- Compressor Contactor (A1)
EQUIP -- Equipment
GND -- Ground
NEC -- National Electrical Code
NOTE: The maximum wire size for C.A1 is 2/0.
Fig. 8 -- Field Power Wiring Connections
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
[_ I I I
TB1 I [] [] []
I I I I
Fig. 9 -- Field Control Thermostat Wiring
Komentáře k této Příručce