Table 2A -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
UNIT
50PG
O6
(cont)
O7
NOMINAL
POWER SUPPLY
Volte-Ph-Hz
VOLTAGE COMPRESSOR OFM POWER ELECTRIC HEAT POWER SUPPLY DISCONNECT
RANGE FLA IFM EXHAUST IFM SIZE
FLA FLA FLA TYPE Nominal MCA MOCPt FLA LRA
Min Max RLA LRA Qty (ea) (ea) FLA kW*
-- -- 10,4 15 10 53
9,2 1O,O 14,0 15 13 53
STD 13,9 15,0 19,9 20 18 53
18.5 2O,O 25,6 30 24 53
23,1 25,0 31.4 35 29 53
-- -- 10,4 15 10 53
9,2 1O,O 14,0 15 13 53
ALT 13.9 15.0 19,9 20 18 53
18.5 2O,O 25,6 30 24 53
23,1 25,0 31.4 35 29 53
575-3-60 518 633 6.1 40 1 0.8 2,0
-- -- 11.8 15 12 55
9,2 1O,O 15,8 20 14 55
STD 13.9 15.0 21,6 25 20 55
18,5 20,0 27,4 30 25 55
1.4 23,1 25,0 33,1 35 30 55
-- -- 11.8 15 12 55
9.2 1O,O 15,8 20 14 55
ALT 13,9 15,0 21,6 25 20 55
18,5 20,0 27,4 30 25 55
23,1 25,0 33,1 35 30 55
-- -- 32.3/32,3 35/35 31/31 182/182
10,0/11.5 3,8/ 5,0 32.3/32,3 35/35 31/31 182/182
15,0/17.3 5,6/ 7,5 32.3/32,3 35/35 31/31 182/182
5,2 -- STD 20,0/23.1 7.5/10,0 32.3/35.4 35/40 31/33 182/182
30,0/34,6 11,3/15.0 44.0/49.8 45/50 40/46 182/182
40,0/46.2 15,0/20.0 56.5/64.3 60/70 52/59 182/182
50,0/57.7 18,8/25.0 69.0/78,6 70/80 63/72 182/182
-- -- 34.6/34,6 35/35 34/34 208/208
10,0/11.5 3,8/ 5,0 34.6/34,6 35/35 34/34 208/208
15,0/17.3 5,6/ 7,5 34.6/34,6 35/35 34/34 208/208
7,5 -- ALT 20,0/23.1 7.5/10,0 34.6/38,3 35/40 34/35 208/208
30,0/34.6 11,3/15.0 46.9/52,6 50/60 43/48 208/208
40,0/46.2 15,0/20.0 59.4/67,1 60/70 55/62 208/208
208/230-3-60 187 253 20,5 149 1 1.5 50,0/57.7 18,8/25.0 71.9/81,5 80/90 66/75 208/208
-- -- 33.7/33,7 35/35 33/33 184/184
10,0/11.5 3,8/ 5,0 33.7/33,7 35/35 33/33 184/184
15,0/17.3 5,6/ 7,5 33.7/33,7 35/35 33/33 184/184
5,2 1.4 STD 20,0/23.1 7.5/10,0 33.7/37,1 35/40 33/34 184/184
30,0/34.6 11,3/15.0 45.8/51,5 50/60 42/47 184/184
40,0/46.2 15,0/20.0 58.3/66,0 60/70 54/61 184/184
50,0/57.7 18,8/25.0 70.8/80,4 80/90 65/74 184/184
-- -- 36.0/36,0 40/40 36/36 210/210
10,0/11.5 3,8/ 5,0 36.0/36,0 40/40 36/36 210/210
15,0/17.3 5,6/ 7,5 36.0/36,0 40/40 36/36 210/210
7,5 1.4 ALT 20,0/23.1 7.5/10,0 36.1/40.0 40/45 36/37 210/210
30,0/34,6 11,3/15.0 48.6/54.4 50/60 45/50 210/210
40,0/46.2 15,0/20.0 61.1/68.9 70/70 56/63 210/210
50,0/57.7 18,8/25.0 73.6/83,3 80/90 68/77 210/210
LEGEND
FLA -- Full Load Amps
NACR -- Heating, Air Conditioning and Refrigeration
IFM -- Indoor (Evaporator) Fan Motor
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code
OFM -- Outdoor (Condenser) Fan Motor
RLA -- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or
600 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.
l-Fuse or HACR circuit breaker,
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker,
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance,
% Voltage Imbalance
= 1OOx max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60.
A a C AB = 224V
BC = 231 v
AC = 226 v
Average Voltage -
224 + 231 + 226
3
681
=--
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 = 224 = 3 v
(BC) 231 = 227 = 4 v
(AC) 227 = 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
4
% Voltage Imbalance = 100 x 22"_-
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
I IMPORTANT: If the supply voltage phase imbalance is more than 2%, 1
contact the local electric utility company immediately.
l