NMH30C000105
CRDR 2689093 Low oil level caused low oil temperature on 2MECBE01.
CRDR 2553858 Several of the normal chillers have tripped due to low lube oil pressure.
CRDR 2421005 Oil leak caused by a loose clamp on an oil line support.
CRDR 2583691 High lube oil tin concentration on chiller 2MWCNE01B (TSC 2674280, TCSAI
2732229)
CRDR 2707271 (U-2) engineering notes anomalies identified while monitoring bearings on chiller
2MWCNE01B.
OE19424 - Repair and Installation of Centrifugal Chiller C UNO Filters (TCS # 2756519)
OE 18597 Junction box cover installation tripped a chiller.
CRDR 3409841 B normal chiller tripped on low oil pressure, due to closed ball valve on oil filter
line,
33MT-9EC01 Essential Chiller
LESSON PLAN REVISION DAT A