7
REMOTE TIMED OVERRIDE — Pressing the timed over-
ride button on the 33ZCT55SPT or 33ZCT56SPT sensors ini-
tiates a timed override. If the override is activated in a zone that
is using a network time schedule, then the override will be re-
ported to the global schedule. When using a global schedule,
all the zones assigned to that schedule will go occupied when
any of the space temperature override buttons are pressed by
the user. For zones that require individual override, those zones
are required to use a local schedule.
If the mode is currently unoccupied and the override func-
tion is activated, the mode will change to occupied for the peri-
od of time configured. The control will interpret a 1 to 10 sec-
ond button press as a user initiated timed override command.
If the override button is held for less than 1 second or more
than 10 seconds, the control will not enter override. If the over-
ride button is held for more than 60 seconds, a Space Tempera-
ture alarm will be generated.
SUPPLY AIR TEMPERATURE SENSOR (SAT) — The
SAT sensor consists of a thermistor encased within a stainless
steel probe. The probe is 6-in. nominal length. See Fig. 3. The
sensor has 114-in. of unshielded, plenum-rated cable (2 con-
ductors, 22 AWG). The range of the sensor is –40 to 185 F with
a nominal resistance of 10,000 ohms at 77 F. The sensor mea-
sures temperature with an accuracy of ± 0.36 F (0.2 C) from
0° to 70 C. The sensor is supplied with a gasket and two self-
drilling mounting screws.
PRIMARY AIR TEMPERATURE SENSOR (PAT) — The
PAT sensor consists of a thermistor encased within a stainless
steel housing with 5-in. of exposed length. See Fig. 4. The sen-
sor has 2 teflon insulated, stranded conductors (24 AWG). The
range of the sensor is –40 to 185 F with a nominal resistance of
10,000 ohms at 77 F. The sensor measures temperature with an
accuracy of ± 0.36 F (0.2 C) from 0° to 70 C.
Table 1 — Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Return-Air
Temperature Sensor, and Supply-Air Temperature Sensor
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
–40 –40 335,651
–35 –31 242,195
–30 –22 176,683
–25 –13 130,243
–20 –4 96,974
–15 5 72,895
–10 14 55,298
–5 23 42,315
0 32 32,651
5 41 25,395
10 50 19,903
15 59 15,714
20 68 12,494
25 77 10,000
30 86 8,056
35 95 6,530
40 104 5,325
45 113 4,367
50 122 3,601
55 131 2,985
60 140 2,487
65 149 2,082
70 158 1,752
.39
.08
FOAM GASKET
.40'' O.D.
.250 ±.01Dia
5.5 ±.5
PLENUM RATED CABLE
114'' +/-6
3.90
3.00
.175 DIA
x .600
3.00
1.50
ø0.50
CLEARANCE HOLE
ENGAGEMENT HOLE FOR
MOUNTING SCREW (2)
Fig. 3 — Supply Air Temperature Sensor Dimensions