PRODUCT DESCRIPTION
The Air Terminal Controller provides dedicated control
functions for a single air terminal and system support functions
for a network of like controllers.
Single Duct Air Terminal Zone Controller
(33ZCVAVTRM) —
The Single Duct Air Terminal Zone
Controller provides dedicated control functions for single duct
terminals with modulating heat or up to 2 stages of heat. The
zone controller is part of the Carrier ComfortID system.
The 33ZCVAVTRM Single Duct Air Terminal Zone Con-
troller provides the following features and benefits:
• capable of demand control ventilation
• provides Pressure Independent (VAV) control
• uses Proportional Integral Derivative (PID) control
• mounts directly onto VAV box damper shaft
• for terminals up to 9000 cfm or 3.4 sq. ft inlet (primary
air)
• auxiliary heating control of modulating (floating) hot
water, single or two-position hot water, single or two-
stage electric, or zone perimeter heat
• quick and easy commissioning and balancing process
• automatic self calibration of airflow transducer
• capable of stand-alone operation
• actuator preassembled to housing
• capable of demand controlled ventilation support with
field-installed IAQ (Indoor Air Quality) sensor
• easy access to airflow sensor pneumatic connections
• Carrier Comfort Network (CCN) compatible
• capable of high-speed 38.4 kilobaud communications
network operation
• 128 controller maximum system (must be located on
same CCN bus segment)
• capable of zone humidity control (dehumidification)
with field-installed humidity sensor
• Carrier Linkage System capability
• global set point and occupancy scheduling
• capable of local set point adjustment with field-installed
temperature sensor (with temperature offset)
• both controller housing and actuator are UL94-5V ple-
num rated
The zone controller is a single duct, variable air volume
(VAV) terminal control with a factory-integrated actuator. The
zone controller maintains precise temperature control in the
space by regulating the flow of conditioned air into the space.
Buildings with diverse loading conditions can utilize reheat
or supplemental heating control. The zone controller can sup-
port two position hot water, modulating hot water, 2-stage elec-
tric, or perimeter heat.
The zone controller provides additional control features
such as Occupied/Unoccupied scheduling initialized via the
network. The zone controller offers override invoked from a
wall sensor during unoccupied hours from 1 to 1440 minutes in
1-minute increments. Optional Indoor Air Quality (IAQ) or rel-
ative humidity monitoring and control are also available. The
Occupied Override function supports Carrier’s Tenant Billing
if the override time is set to values of 1, 2, 3, or 4 hours (60,
120, 180, or 240 minutes).
The zone controller control assembly contains an integral
VAV actuator assembly that is field mounted to the VAV termi-
nal damper shaft, similar to the mounting of a standard actua-
tor. The actuator is rated at 35 lb.-in. (3.95 N-m) torque, a
90-degree stroke, and provides a 90-second nominal time at
60 Hz. The actuator is suitable for mounting onto a
3
/
8
-in.
(9.5 mm) square or round damper shaft, or onto a
1
/
2
-in.
(13 mm) round damper shaft. The minimum damper shaft
length is 1
3
/
4
-in. (45 mm). The zone controller is designed for
vertical or horizontal mounting.
The zone controller is provided with removable connectors
for power and communications. The zone controller has non-
removable screw type connectors for inputs. The removable
connectors are designed so that they can be inserted one way so
as to prevent installation errors. The zone controller also pro-
vides an RJ-11 modular phone jack for the Network Service
tool connection to the module via the Carrier Comfort Network
(CCN) communications.
An optional Conduit Box Cover (Part Number
33ZCCONBOX) allows field wiring connection via conduit.
The conduit box is designed to accept two
1
/
2
-in. (13 mm)
EMT conduits.
The 33ZCVAVTRM is designed to allow a service person
or building owner to configure and operate the unit through the
CCN user interfaces. A user interface is not required for day-
to-day operation. All maintenance, configuration, setup, and
diagnostic information is available through the Level II com-
munications port to allow data access by an attached computer
running Network Service Tool, ComfortVIEW
™
, or Comfort-
WORKS
®
software.
WIRING CONNECTIONS — Field wiring is 18 to 22 AWG
(American Wire Gage). The zone controller is a NEC (National
Electrical Code) Class 2 rated device.
INPUTS
• space temperature sensor
• primary air damper position (factory-installed)
• airflow sensor (factory installed)
• remote wall sensor set point adjustment
• optional supply temperature sensor (required for ducted
heat)
• optional primary air temperature sensor (required for
systems which do not utilize a linkage compatible air
source system)
• optional IAQ sensor or relative humidity sensor
• optional remote occupancy contact
OUTPUTS
• internally factory-wired damper actuator
• heating (ducted or non-ducted)
— modulating (floating) heat
— up to 2 stages of electric heat (if 3 stages are required,
the 33ZCFANTRM should be used)
— two position heat
POWER SUPPLY
The 33ZCVAVTRM zone controller requires a 24 VAC ±
10% at 40 VA (50/60 Hz) power source.
POWER CONSUMPTION — The power requirement siz-
ing allows for accessory water valves or heat contactors. Water
valves are limited to 15 VA on both two-position and modulat-
ing hot water. The heat contactors are limited to 10 VA (hold-
ing) each.
ACCURACY — Terminal airflow (nominal cfm) is rated at
1-in. wg (249 kPa) measured velocity pressure. The zone con-
troller is capable of controlling to as low as 10% or as high as
125% of nominal airflow with an accuracy of ± 3% (nominal)
at any point within the range.
HARDWARE (MEMORY)
FLASH EPROM
DIFFERENTIAL PRESSURE RANGE
0 to 2.0 in. wg (0 to 498 kPa) maximum for the onboard
flow sensor.
→