Carrier PC211 Specifikace Strana 1

Procházejte online nebo si stáhněte Specifikace pro ne Carrier PC211. Carrier PC211 Specifications Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 116
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 211 Catalog No. 532-306 Printed in U.S.A. Form 23XL-3SS Pg 1 7-99 Replaces: New
Book 2
Tab 5e
Start-Up, Operation and Maintenance
Instructions
SAFETY CONSIDERATIONS
Screw liquid chillers are designed to provide safe and
reliable service when operated within design specifica-
tions. When operating this equipment, use good judgment
and safety precautions to avoid damage to equipment and
property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions, as
well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accor-
dance with the latest edition of ANSI/ASHRAE 15 (American
National Standards Institute, American Society of Heating, Refrigera-
tion, and Air Conditioning Engineers), latest edition. The accumula-
tion of refrigerant in an enclosed space can displace oxygen and cause
asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead spaces. Inha-
lation of high concentrations of vapor is harmful and may cause heart
irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is
heavier than air and reduces the amount of oxygen available for
breathing. Product causes eye and skin irritation. Decomposition
products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
NEVER EXCEED specified test pressures. VERIFY the allowable
test pressure by checking the instruction literature and the design pres-
sures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and the
work area should be well ventilated. Refrigerant in contact with an
open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control cen-
ters, switches, starters, or oil heater (if applicable) until you are sure
ALL POWER IS OFF and no residual voltage can leak from capaci-
tors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
DO NOT syphon refrigerant.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY
FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar, and
unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause dam-
age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those cited
herein should comply with ANSI/ASHRAE 15 (latest edition). Con-
tact Carrier for further information on use of this chiller with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
chiller is under pressure or while chiller is running. Be sure pressure is
at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the
device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Fol-
low safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if compo-
nents are light, use mechanical equipment when there is a risk of slip-
ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fan, or pumps. Shut off the
chiller or pump before servicing equipment.
USE only repair or replacement parts that meet the code requirements
of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
23XL
Hermetic Screw Liquid Chillers with HCFC-22
and HFC-134a, 50/60 Hertz
PIC II Controls
Zobrazit stránku 0
1 2 3 4 5 6 ... 115 116

Shrnutí obsahu

Strany 1 - Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Strany 2 - CONTENTS

10LEGENDFig. 3 — Refrigerant Oil Flow Schematic (TC Frame 1 and 2 Chillers)HGBP —Hot Gas BypassRefrigerant Liquid FlowRefrigerant Vapor FlowOil and Re

Strany 3 - CONTENTS (cont)

100AUX — AuxiliaryBR — Bridge RectifierCB — Circuit BreakerCOMM — CommunicationCOND — CondenserCPU — Central Processing UnitCVC — Chiller Visual Contr

Strany 4 - INTRODUCTION

101Fig. 50 — Typical Wye Delta Free-Standing Starter Wiring Schematic (Low Voltage)LEGENDAUX — AuxiliaryCB — Circuit BreakerCOMM — CommunicationCOND —

Strany 5 - System Components —

102Fig. 51 — Typical Solid-State Free-Standing Starter Wiring Schematic (Low Voltage)NOTES:PFC — Power Factor Contactor1M CONTACTAUX — Closes when SCR

Strany 6 - FRONT VIEW

103LEGEND*Field supplied terminal strip must be located in the control center.Fig. 52 — Typical COMM1 CCN Communication Wiring for Multiple ChillersFa

Strany 7

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Strany 8

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Strany 9 - Oil Loss Prevention —

CL-2INSPECT WIRING AND RECORD ELECTRICAL DATA:RATINGS:Motor VoltageMotor(s) Amps Starter LRA RatingLine Voltages: Motor Controls/Oil HeaterFIELD-INSTA

Strany 10

CL-3CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 11

CL-4NOTE: Default setting is OCCUPIED 24 hours/day.NOTE: Default setting is UNOCCUPIED 24 hours/day.NOTE: Default setting is OCCUPIED 24 hours/day.23X

Strany 12 - STARTING EQUIPMENT

CL-5CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 13

11LEGENDFig. 4 — Refrigerant Oil Flow Schematic (TD Frame 4 Chillers)HGBP —Hot Gas BypassRefrigerant Liquid FlowRefrigerant Vapor FlowOil and Refriger

Strany 14 - PIC II System Components —

CL-623XL PIC II OPTIONS TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUEAuto Restart Option0/1 DSABLE/ENABLE DSABLERemote Contacts Optio

Strany 15

CL-7CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 16

CL-823XL PIC II SETUP2 TABLE CONFIGURATION SHEETDESCRIPTION STATUS UNITS DEFAULT VALUECapacity ControlProportional Inc Band2 to 10 6.5Proportional Dec

Strany 17

CL-9CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 18 - Fig. 15 — Control Panel

CL-1023XL PIC II RAMP_DEM TABLE CONFIGURATION SHEET23XL PIC II TEMP_CTL TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUEPulldown Ramp Ty

Strany 19 - 21.8 132.9 93

CL-11CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Strany 20

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Strany 21

12Slide Valve Principle — Oil flow to the slide piston iscontrolled by two solenoid valves. Each solenoid is operatedby load and unload signals from t

Strany 22

13Unit-Mounted Solid-State Starter (Optional) —The 23XL chiller may be equipped with a solid-state, reduced-voltage starter (Fig. 8 and 9). This start

Strany 23

14CONTROLSDefinitionsANALOG SIGNAL — An analog signal varies in proportionto the monitored source. It quantifies values between operatinglimits. (Exam

Strany 24

15*Some 23XL chillers will have both an oil temperature sensor and an oil level safety switch (two separate components).Fig. 11 — 23XL Control and Sen

Strany 25

16*Some 23XL chillers will have both an oil temperature sensor and an oil level safety switch (two separate components).Fig. 12 — 23XL Control and Sen

Strany 26 - Table 3 — CVC Display Data

17INTEGRATED STARTER MODULE (ISM) — This mod-ule is located in the starter cabinet. This module initiates com-mands from the CVC for starter function

Strany 27

18Fig. 15 — Control PanelFig. 16 — Power Panel

Strany 28

19CVC Operation and Menus (Fig. 17-23)GENERAL• The CVC display automatically reverts to the defaultscreen after 15 minutes if no softkey activity take

Strany 29

2CONTENTSPageSAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 30

20• Press to leave the selected decision or field with-out saving any changes.• Press to leave the selected decision or field andsave changes.• Pr

Strany 31

21CCNLOCAL RESETMENUDEFAULT SCREENStart Chiller In CCN ControlStart Chiller in Local ControlClear AlarmsSTATUSSCHEDULE SETPOINTSERVICE(SOFTKEYS)Access

Strany 32

22NEXTPREVIOUSSELECTEXITSERVICE TABLEDisplay Alarm History(The table holds up to 25 alarms and alerts with the most recent alarm at the top of the s

Strany 33

23NEXTPREVIOUSSELECTEXITSERVICE MENU CONTINUEDFROM PREVIOUS PAGESelect a Service TableSelect a Service Table ParameterNEXTPREVIOUSSELECTEXITModify a S

Strany 34

242. Press to select the highlighted value. Then:For Discrete Points — Press or toselect the desired state.For Analog Points — Press or to sel

Strany 35

25b. Press to select days in the day-of-weekfields. Press to eliminate days from theperiod.7. Press to register the values and to move hori-zont

Strany 36

26Table 3 — CVC Display Data1. Only 12 lines of information appear on the CVC screen at anyone time. Press the or softkey to highlighta point or t

Strany 37 - PIC II System Functions

27Table 3 — CVC Display Data (cont)EXAMPLE 2 — MAINTSTAT DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press ( will

Strany 38 - Ramp Loading —

28 Table 3 — CVC Display Data (cont)EXAMPLE 4 — COMPRESS DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. Scrol

Strany 39

29Table 3 — CVC Display Data (cont)EXAMPLE 6 — POWER DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. Scroll

Strany 40

3CONTENTS (cont)PagePower Up the Controls andCheck the Oil Heater . . . . . . . . . . . . . . . . . . . . . . . . . . 60• SOFTWARE VERSIONSoftware Con

Strany 41 - Fig. 24 and 25) —

30Table 3 — CVC Display Data (cont)EXAMPLE 8 — SETPOINT DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press (Base De

Strany 42 - Lead/Lag Control —

31Table 3 — CVC Display Data (cont)EXAMPLE 10 — OVERRIDE DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. S

Strany 43

32Table 3 — CVC Display Data (cont)EXAMPLE 12 — ISM_HIST DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. S

Strany 44 - Ice Build Control —

33Table 3 — CVC Display Data (cont)EXAMPLE 14 — NET_OPT DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. Sc

Strany 45

34Table 3 — CVC Display Data (cont)EXAMPLE 16 — OPTIONS DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. Sc

Strany 46 - Service Operation —

35Table 3 — CVD Display Data (cont)EXAMPLE 17 — SETUP1 DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. Scr

Strany 47 - Local Start-Up —

36Table 3 — CVD Display Data (cont)EXAMPLE 19 — LEAD/LAG DISPLAY SCREENTo access this display from the CVC default screen:1. Press .2. Press .3. S

Strany 48 - Shutdown Sequence —

37PIC II System FunctionsNOTE: Words not part of paragraph headings and printed in allcapital letters can be viewed on the CVC (e.g., LOCAL, CCN,RUNNI

Strany 49

38CONFIGURATION table. See Table 3, Example 14. SCHED-ULE NUMBER can be changed to any value from 03 to 99. Ifthis number is changed on the NET_OPT sc

Strany 50 - Leak Test Chiller —

391. The slide is prevented from closing further, and thestatus line on the CVC indicates the reason for theoverride.2. The slide valve is opened unti

Strany 51

4CONTENTS (cont)PageChecking Pressure Transducers. . . . . . . . . . . . . . . . .77• COOLER CONDENSER PRESSURE TRANSDUCER AND WATERSIDE FLOW DEVICE C

Strany 52

40Table 5 — Capacity Overrides Table Capacity OverridesRemote Start/Stop Controls — A remote device,such as a timeclock that uses a set of contacts,

Strany 53

41vessels changes. This prevents low condenser water tempera-ture and maximizes chiller efficiency. The tower fan relay canonly accomplish this if the

Strany 54 - (TC Frame 1 and 2 Chillers)

42The algorithm first determines if corrective action is neces-sary. This is done by checking two sets of operator configureddata points, which are th

Strany 55 - (TD Frame 4 Chillers)

43If leaving chilled water control (ECW CONTROL OPTIONis set to 0 [DSABLE], TEMP_CTL screen) and a commonpoint sensor is desired (COMMON SENSOR OPTION

Strany 56

44Lag Chiller Shutdown Requirements — The following con-ditions must be met in order for the lag chiller to be stopped.1. Lead chiller compressor moto

Strany 57

45ICE BUILD INITIATION — The ice build time schedule(OCCPC02S) is the means for activating the ice build option.The ice build option is enabled if

Strany 58

46When the ATTACH TO NETWORK DEVICE screen is ac-cessed, information can not be read from the CVC on any de-vice until one of the devices listed on th

Strany 59 - Check Starter

47days of the week field signifies that the period is applicable to aholiday. (See Fig. 22.)The broadcast function must be activated for the holidaysc

Strany 60

48If the water/brine temperature is high enough, the start-upsequence continues and checks the slide valve unload timer. Ifthe unload timer has expire

Strany 61

49The soft stop amps threshold function can be terminated andthe compressor motor deenergized immediately by depressingthe STOP button twice.Chilled W

Strany 62

5ABBREVIATIONS AND EXPLANATIONSFrequently used abbreviations in this manual include:Words printed in all capital letters or in italics may beviewed on

Strany 63 - High Altitude Locations —

50Leak Test Chiller — Due to regulations regarding refrig-erant emissions and the difficulties associated with separatingcontaminants from refrigerant

Strany 64

51Fig. 31 — 23XL Leak Test Procedure

Strany 65 - Preparation —

52Fig. 32 — Typical Optional Pumpout System Piping Schematic with Storage Tank (TC Frame 1 and 2 Chillers)

Strany 66

53Fig. 33 — Typical Optional Pumpout System Piping Schematic With Storage Tank (TD Frame 4 Chillers)

Strany 67

54Fig. 34 — Typical Optional Pumpout System Piping Schematic Without Storage Tank(TC Frame 1 and 2 Chillers)

Strany 68

55Fig. 35 — Typical Optional Pumpout System Piping Schematic Without Storage Tank(TD Frame 4 Chillers)

Strany 69 - Preparation —

56Table 6A — HCFC-22 Pressure — Temperature (F)Table 6B — HCFC-22 Pressure — Temperature (C)TEMPERATURE(F)PRESSURE (psi)Absolute Gage–5011.67 6.154*–4

Strany 70

57Table 6C — HFC-134a Pressure — Temperature (F) Table 6D — HFC-134a Pressure — Temperature (C)TEMPERATURE, F PRESSURE (psig)06.5027.5248.6069.66810.7

Strany 71

58Chiller Dehydration — Dehydration is recommended ifthe chiller has been open for a considerable period of time, ifthe chiller is known to contain mo

Strany 72

593. Compare the ampere rating on the starter nameplate torating on the compressor nameplate. The overload tripamps must be 108% to 120%of the rated l

Strany 73

6131415161718524232221 20 191197252651027121237654111098Fig. 2A — Typical 23XL Installation (TC Frame 1 and 2 Chillers)1—Power Panel2—Chiller Visual C

Strany 74

60attached to the starter frame near the relays. Useonly the dashpot oil supplied with the starter. Do notsubstitute.Solid-state overload relays do no

Strany 75

61TO CHANGE THE PASSWORD — The password may bechanged from the CVC CONFIGURATION screen.1. Press the and softkeys. Enter thecurrent password and h

Strany 76 - Overview —

62Modify Minimum and Maximum Load Points (∆T1/P1;∆ T2/P2) If NecessaryT — These pairs of chiller load points,located on the OPTIONS screen, determine

Strany 77 - Checking Display Messages —

63Perform a Control Test — Check the safety controlsstatus by performing an automated control test. Access theCONTROL TEST table and select a test to

Strany 78 - LEGEND TO TABLES 9A-9J

64Table 7 — Control Test Menu FunctionsCharge Refrigerant into ChillerThe standard 23XL chiller is shipped with the refrigerant al-ready charged in th

Strany 79 - C. IN RECYCLE SHUTDOWN

65The full refrigerant charge on the 23XL will vary with chill-er components and design conditions, as indicated on the jobdata specifications. An app

Strany 80 - E. START-UP IN PROGRESS

66To Prevent Accidental Start-Up — A chiller STOPoverride setting may be entered to prevent accidental start-upduring service or whenever necessary. A

Strany 81 - H. OUT-OF-RANGE SENSOR ALARMS

67water temperature to save on compressor kilowattrequirements but, not be below 55 F (12.8 C).6. Cooler pressure and temperature also will vary witht

Strany 82

68Plant MODEL NO. SERIAL NO. REFRIGERANT TYPE REMARKS: Indicate shutdowns on safety controls, repairs made, oil or refrigerant added or removed,

Strany 83

69PUMPOUT AND REFRIGERANTTRANSFER PROCEDURESPreparation — The 23XL may come equipped with anoptional pumpout storage tank, pumpout system, or pumpoutc

Strany 84 - J. CHILLER ALERTS

7123451211 109876181716151413192021222324253130 2928826273534333212Fig. 2B — Typical 23XL Installation (TD Frame 4 Chiller)1—Compressor Nameplate (Hid

Strany 85 - J. CHILLER ALERTS (cont)

70Chillers with Isolation ValvesTRANSFER ALL REFRIGERANT TO CHILLER CON-DENSER VESSEL — For chillers with isolation valves, re-frigerant can be store

Strany 86

71Chillers with Storage Tanks — If the chiller has aseparate storage tank, or the chiller does not have isolationvalves, refer to the following proced

Strany 87

72GENERAL MAINTENANCERefrigerant Properties — HCFC-22 and HFC-134aare the standard refrigerants in the 23XL. At normal atmo-spheric pressure, HCFC-22

Strany 88 - Notes on Module Operation

73WEEKLY MAINTENANCECheck the Lubrication System — Mark the oil lev-el on the sight glasses and observe the level each week whilethe chiller is shut d

Strany 89 - Solid-State Starters —

7411. Add oil (approximately 4.2 gal [15.9 L]) until it can beseen at the lower edge of the oil sump sight glass. Theoil sight glass will not fill com

Strany 90 - INTEGRATED STARTER MODULE

75As a minimum, the following maintenance is required.1. At least once a year, disconnect the vent piping at thevalve outlet and carefully inspect the

Strany 91

76Inspect starter contact surfaces for wear or pitting on me-chanical-type starters. Do not sandpaper or file silverplatedcontacts. Follow the starter

Strany 92 - Physical Data —

77• If an operating fault is detected, an alarm message isgenerated and displayed on the CVC default screen. Amore detailed message — along with a dia

Strany 93

784. A high pressure point can also be calibrated between25 and 250 psig (172.4 and 1723.7 kPa) by attaching aregulated 250 psig (1724 kPa) pressure (

Strany 94

79Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides A. MANUAL STOPB. READY TO STARTC. IN RECYCLE

Strany 95

8Cooler — This vessel (also known as the evaporator) islocated underneath the compressor. The cooler is maintained atlow temperature/pressure so that

Strany 96

80Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)D. PRE-START ALERTS: These alerts only

Strany 97

81 Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)F. NORMAL RUNG. NORMAL RUN WITH OVERR

Strany 98

82Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECT LIMIT FAULTS*[LIMIT

Strany 99

83Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECT LIMIT FAULTS (cont)

Strany 100

84Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECT LIMIT FAULTS (cont)

Strany 101

85Table 9 — CVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)J. CHILLER ALERTS (cont)*[LIMIT] is sh

Strany 102

86Table 10A — Thermistor Temperature (F) vs Resistance/VoltageDropTEMPERATURE(F)VOLTAGEDROP (V)RESISTANCE(Ohms)–254.821 98,010–244.818 94,707–234.814

Strany 103

87Table 10B — Thermistor Temperature (C) vs Resistance/Voltage DropTEMPERATURE(C)VOLTAGEDROP (V)RESISTANCE(Ohms)–404.896 168 230–394.889 157 440–384.8

Strany 104

88Control Modules — Turn controller power off beforeservicing controls. This ensures safety and prevents damage tothe controller.The CVC, CCM, and ISM

Strany 105 - INITIAL START-UP CHECKLIST

89Chiller Control Module (CCM) (Fig. 43)INPUTS — Each input channel has 2 or 3 terminals. Refer toindividual chiller wiring diagrams for the correct t

Strany 106

9supply and equalize oil pressure to and around the pis-ton. This allows the slide valve to unload and load.• seals the gap between the male and femal

Strany 107

90STATCOMM THERMISTORSJ4DIFF PRESSUREJ3PRESSUREJ2SW2V/I INPUTSJ5SIOJ7ANALOG OUTJ8J11DISCRETEOUTPUTSJ12DISCRETEOUTPUTSJ124 VACSIOJ6INTEGRATED STARTER M

Strany 108

915. Using an ohmmeter, perform the following resistancemeasurements and record the results:If all measured values are greater than 5K ohms, pro-ceed

Strany 109

92Physical Data — For operator convenience during trou-bleshooting, additional details regarding compressor torquespecifications, physical data, elect

Strany 110

93Table 14A — 23XL Waterbox Cover Weights (Frame 1 and 2 Machines)*LEGENDNIH — Nozzle-In-Head*These weights are given for reference only. They have be

Strany 111

94Table 15 — Optional Storage Tank and/or Pumpout System Physical DataLEGENDNOTES:1. ANSI/ASHRAE 15 — Safety Code for Mechanical Refrigeration2. Dry w

Strany 112

95Table 18 — 23XL Compressor Torque Specification Chart for Metric amd American FastenersITEMCAP SCREWSIZE AND TYPEGRADE ASSEMBLY LOCATIONTORQUENm Lb-

Strany 113

96Fig. 46 — 23XL Chiller Control SchematicDenotes Component TerminalWire SpliceDenotes ConductorMale/Female ConnectorOption WiringLEGENDCB — Circuit B

Strany 114

97Fig. 47 — Power Panel Wiring SchematicCB —Circuit BreakerCCM —Chiller Control ModuleHGBP —Hot Gas BypassISM —Integrated Starter ModuleTB —Terminal B

Strany 115

98Fig. 48 — Cutler-Hammer Wye Delta Unit Mounted Starter Wiring Schematic (Low Voltage).For connection diagram refer to 261143 D4.Yellow wires remain

Strany 116

99Fig. 49 — Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic (Low Voltage)

Komentáře k této Příručce

Žádné komentáře