11
Water connections (30GY/GV 044-059)
There are two alternatives:
- Water entering at the left of the duplex unit and leaving on
the right.
- Water entering at the right of the duplex unit and leaving
on the left.
The water inlet must be on one evaporator, and the outlet on
the other one, in order to correctly balance the flow rates in the
evaporators. When installing and connecting the components
ensure that there is no leak at any of the connections (see
diagram below).
IMPORTANT: The heat exchanger can be damaged by frost in
winter. Depending on the atmospheric conditions in your area
you can:
- Add ethylene glycol.
- Increase the thickness of the insulation.
- Never disconnect the evaporator heaters.
- If the unit is not used for a prolonged period, empty the
the heat exchanger and add ethylene glycol. At the
beginning of the following season, again fill the unit with
water and an added inhibitor.
If auxiliary equipment is installed, the installer must
follow basic installation principles and ensure that the
minimum and maximum flow rates are not exceeded; the
values must be between the values given in the Physical
Data table.
Water connections (30GV/GY 044-059)
Evaporator 1
Evaporator 2
Evaporator 2
Evaporator 1
Refrigerant inlet and outlet
Refrigerant inlet and outlet
First alternative
Second alternative
Water outlet
Water inlet
Water outlet
Water inlet