START-UP PROCEDURES
Step 1—Finishing the Job
1. Hide the tubing where possible.
2. Make sure that the drainage tube slopes downwards along its
entire length.
3. Insulate tubing and connections.
4. Fasten tubes to the outside wall.
5. Seal the hole through which the cables and tubing pass.
6. Connect the air conditioner to the power source and turn it on.
7. Check all air conditioner operating modes. Consult the User
Manual.
INDOOR UNIT
1. Do all the remote controller buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drainage work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
2. Is noise, drain water or air flow from the unit likely to disturb
the neighbors?
3. Are there any gas leaks?
EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER,
WITH THE AID OF THE USER MANUAL:
1. How to turn the air conditioner on and off; selecting cooling,
heating and other operating modes; setting a desired tempera-
ture; setting the timer to automatically start and stop air
conditioner operation; and the other features of the remote
controller and display panel.
2. How to remove and clean the air filter.
3. How to set the air deflection louver.
4. Present the User Manual and this installation sheet to the
customer.
Table 4—Electrical Data - Indoor Unit
MODEL 40CG-018 40CG-024 40CG-030 40CS-018 40CS-024 40CS-030
MCA 0.8 0.8 0.8 11.5 17.0 17.0
MOCP 15 15 15 20 30 30
Power Supply 208/230V, 60 Hz, 1 Ph
Full Load Amps 0.6 0.6 0.6 8.9 13.1 13.1
Fan Motor Amps 0.6 0.6 0.6 0.6 0.6 0.6
Electric Heater (watts) n/a n/a n/a 2000 3000 3000
Electric Heater (amps) n/a n/a n/a 8.3 12.5 12.5
Specifications and performance data are subject to change without notice.
MCA–Minumum Circuit Amps
MOCP–Maximum Over Current Protection
Table 5—Electrical Data - Outdoor Unit
MODEL 40CG-018 40CG-024 40CG-030 40CS-018 40CS-024 40CS-030
MCA 11.4 14.1 19.8 22.1 30.4 36.1
MOCP 15 20 30 25 35 40
Power Supply 208/230V, 60 Hz, 1 Ph
Fan Motor Amps 1.5 1.5 1.5 1.5 1.5 1.5
Full Load Amps 7.4 9.6 14.2 7.4 9.6 14.2
Locked Rotor Amps 48.0 61.0 94.0 48.0 61.0 94.0
Specifications and performance data are subject to change without notice.
MCA–Minumum Circuit Amps
MOCP–Maximum Over Current Protection
Fig. 22—Dimensional Drawing
OPEN
SIZE
BACK OPENINGS
23 4 567
A
(in.) 9.1 13.4 17.7 22.1 26.4 30.7
(mm) 230 340 450 560 670 780
B
(in.) 11.2 15.5 19.85 24.2 28.5 32.8
(mm) 284 394 504 514 724 834
A01101
WALL
THICKNESS
A
B
173(6.8”)
45(1.8”)
12(0.5”) min
112(4.4”)
Fig. 23—Two Way Air Conditioner
A01102
WALL
REAR AIR
OUTLET
EVAPORATOR
WOODEN
FRAME
REAR
OUTLET
GRILL
AIR
FEEDBACK
GRILLE
PVC
TUBE
AIR
FEEDBACK
OPENING
SPONGY
GASKET