Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...1GENERAL ...1INSTAL
Procedure for Using the Refrigerant Receiver (Fig. 9)During Normal Operation — Valve A is open and valves Band C are closed. Receiver is isolated from
Table 3 — Minimum Refrigerant Line Size DataUNIT09BYLENGTH OF PIPE0to15ft 16to25ft 26to50ft 51to75ft 76to100ftQtyHot GasLine(in.)LiquidLine(in.)QtyHot
3. A high-density fiberglass (2 lb minimum density) or semi-rigid foamed insulation such as Styrofoam™ will be re-quired inside the ducts to prevent ai
GENERAL — Verify that nameplate electrical requirementsmatch available power supply. Voltage at condenser must bewithin the minimum and maximum shown
Condenser operation on improper line voltage or exces-sive phase imbalance may be considered abuse and any re-sulting damage may not be covered by Car
START-UPTo prevent personal injury, be sure wire fan guards aresecured in place over each fan discharge (or that fansare ducted) before starting the u
Table 5 — Condenser Fan PerformanceUNIT09BYSTATIC PRESSURE (in. wg)CFM0.0 0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp0062000 67
TO CHANGE FAN WHEEL — If a fan wheel should fail,it may be replaced as follows:1. Remove belts from fan pulley.2. Loosen locking collars on the fan be
Copyright 1999 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and w
START-UP CHECKLISTA. Preliminary InformationCOMPRESSOR BEARING UNIT: MODEL NO. SERIAL NO.09BY UNIT: MODEL NO. SERIAL NO.FIELD-INSTALLED ACCESSORIESB.
VIEW A-A006-014 UNIT SIZEVIEW A-A008-014 UNIT SIZEVIEW B-B016-024 UNIT SIZEFig. 1 — 09BY UnitsRIGHT SIDE VIEW REAR VIEW (HORIZONTAL DISCHARGE) LEFT SI
CHECK VOLTAGE IMBALANCEIS CONDENSER MOTOR WIRED FOR CORRECT VOLTAGE? (Y/N)LINE-TO-LINE VOLTS: AB VACVBCV(AB + AC + BC)/3 = AVERAGE VOLTAGE =VMAXIMUM D
LEGENDRefrigerant ConnectionField-Supplied Refrigerant Piping*Field-Supplied Floor Stand (Height to Match Wall Opening).09BYDISCHARGEDUCTINLETDUCTTO O
09BY DIMENSIONS (English)DIMENSION006(Ft-in.)008(Ft-in.)012(Ft-in.)014(Ft-in.)016,024(Ft-in.)A 2-111⁄23- 613⁄163- 613⁄163- 613⁄165- 0B 1- 711⁄161-115⁄
36" MIN.REQUIREDSEE NOTE 2ELECTRICALACCESS36"CORNER CCORNER BAIRFLOWALLOW ACCESSTO CLEANCONDENSERCOIL36"RECOMMENDEDBELT
Table 1 — Indoor Circuit/Condenser ApplicationUNIT50BZ09BY006 008 012 014 016 024006 SO008 SO*012 SO014 SO016 SOLEGENDS—StandardO—Optional*Field manif
Step 2 — Rig and Place UnitRIGGING — The 09BY units are mounted on skids. Leavethe unit on the skid until it is in the final position. While onthe skid
Step 3 — Install Accessory Low-Ambient Kit orInlet Filter Kit (If Required) (See Fig. 7) —If theunit will be operated with inlet air to the condenser
Step 4 — Install Rain Drain (See Fig. 8)IMPORTANT: A rain drain connection MUST BEUSED if any possibility exists of rain water enteringthe unit.The 09