APPENDIX A CCN TABLES (cont)
CURRMODS
SETPOINT
LOADFACT
VERSIONS
DESCRIPTION STATUS UNITS POINT
FSM controlling chiller ON/OFF MODE_1
WSM controlling chiller ON/OFF MODE_2
Master/Slave control ON/OFF MODE_3
Low source protection ON/OFF MODE_4
Ramp Load Limited ON/OFF MODE_5
Timed Override in effect ON/OFF MODE_6
Low Cooler Suction TempA ON/OFF MODE_7
Low Cooler Suction TempB ON/OFF MODE_8
Slow Change Override ON/OFF MODE_9
Minimum OFF Time ON/OFF MODE_10
Low Suction Superheat A ON/OFF MODE_11
Low Suction Superheat B ON/OFF MODE_12
Dual Setpoint ON/OFF MODE_13
Temperature Reset ON/OFF MODE_14
Demand Limit in effect ON/OFF MODE_15
Cooler Freeze Prevention ON/OFF MODE_16
Lo Tmp Cool/Hi Tmp Heat ON/OFF MODE_17
Hi Tmp Cool/Lo Tmp Heat ON/OFF MODE_18
Making Ice ON/OFF MODE_19
Storing Ice ON/OFF MODE_20
High SCT Circuit A ON/OFF MODE_21
High SCT Circuit B ON/OFF MODE_22
DESCRIPTION STATUS UNITS POINT DEFAULTS
COOLING
Cool Setpoint 1 20 to 70 °F CSP1 44
Cool Setpoint 2 20 to 70 °F CSP2 44
Ice Setpoint 20 to 42 °F CSP3 42
HEATING
Heat Setpoint 1 80 to 140 °F HSP1 100
Heat Setpoint 2 80 to 140 °F HSP2 100
RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 °F/min CRAMP 1.0
Heating Ramp Loading 0.2 to 2.0 °F/min HRAMP 1.0
HEAD PRESSURE
Head Pressure Setpoint A 80 to 140 °F HSP_A 113
Head Pressure Setpoint B 80 to 140 °F HSP_B 113
DESCRIPTION STATUS UNITS POINT
CAPACITY CONTROL
Load/Unload Factor snnn.n % SMZ
Control Point snnn.n °F CTRL_PNT
Leaving Water Temp snnn.n °FLWT
DESCRIPTION STATUS UNITS POINT
MBB CESR-131170 nn-nn
EXV CESR-131172 nn-nn
CXB CESR131173- nn-nn
EMM CESR131174- nn-nn
MARQ CESR131171- nn-nn
NAV CESR131227- nn-nn