11
HEATING PERFORMANCE DATA -- 38/40MFQ (HEAT PUMP)
Model
38---40MFQ
Heating Outdoor conditions (DB) ° F
Indoor Conditions
DB ° F
(BTU/h) 53.6 44.6 39.2 32.0 24.8 19.4
009
59
TC 11.30 11.00 11.91 7.70 6.44 6.20
Input 1.20 1.17 1.28 1.11 1.03 1.08
64.4
TC 10.64 10.44 11.53 7.32 6.76 5.97
Input 1.23 1.17 1.30 1.18 1.14 1.19
69
TC 10.58 10.55 11.43 6.95 6.25 6.10
Input 1.26 1.21 1.34 1.18 1.11 1.17
71.6
TC 9.84 10.26 10.90 5.90 6.31 5.89
Input 1.16 1.20 1.34 1.17 1.12 1.23
012
(115v)
59
TC 12.81 12.12 12.00 7.76 6.48 6.25
Input 1.44 1.37 1.37 1.18 1.10 1.16
64.4
TC 12.06 11.50 11.61 7.37 6.80 6.01
Input 1.47 1.37 1.39 1.26 1.21 1.27
69
TC 12.00 11.62 11.51 7.00 6.30 6.15
Input 1.51 1.41 1.43 1.26 1.19 1.25
71.6
TC 11.15 11.30 10.98 5.94 6.36 5.94
Input 1.40 1.40 1.43 1.25 1.20 1.31
012
(208---230v)
59
TC 12.79 12.11 11.98 7.75 6.48 6.24
Input 1.44 1.37 1.37 1.18 1.10 1.16
64.4
TC 12.05 11.49 11.59 7.36 6.80 6.00
Input 1.47 1.37 1.40 1.26 1.22 1.27
69
TC 11.98 11.61 11.49 6.99 6.29 6.14
Input 1.51 1.42 1.43 1.26 1.19 1.25
71.6
TC 11.14 11.29 10.97 5.94 6.35 5.93
Input 1.40 1.41 1.43 1.26 1.20 1.31
017
59
TC 20.22 19.47 18.52 11.97 10.01 9.65
Input 2.19 2.12 2.04 1.76 1.64 1.73
64.4
TC 19.04 18.48 17.92 11.38 10.51 9.28
Input 2.24 2.12 2.08 1.87 1.81 1.90
69
TC 18.94 18.66 17.77 10.81 9.72 9.49
Input 2.30 2.19 2.13 1.87 1.77 1.87
71.6
TC 17.61 18.15 16.95 9.18 9.82 9.16
Input 2.13 2.18 2.13 1.87 1.79 1.96
022
59
TC 24.12 23.15 21.97 14.20 11.87 11.44
Input 2.19 2.11 2.03 1.74 1.62 1.71
64.4
TC 22.71 21.97 21.26 13.50 12.46 11.01
Input 2.24 2.11 2.06 1.86 1.79 1.88
69
TC 22.59 22.19 21.07 12.82 11.53 11.26
Input 2.30 2.18 2.11 1.86 1.76 1.85
71.6
TC 21.00 21.59 20.11 10.89 11.64 10.87
Input 2.13 2.16 2.12 1.85 1.77 1.94
LEGEND
DB --- Dry Bulb
TC --- Total Net Cooling Capacity (1000 Btu/hour)
I n pu t --- To t a l Po w e r ( k W )