4
62EBA AND 62E7A PERFORMANCE RATINGS
Type: WHEEL
Nominal Airflow: 350 cfm
Tilt Angle (Heating/Cooling): N/A Degrees
Pressure Drop: 0.38 inches
THERMAL EFFECTIVENESS RATINGS AT
0 in. PRESSURE DIFFERENTIAL
LEAKAGE RATINGS
LEGEND
62EAC AND 62E1C PERFORMANCE RATINGS
Type: WHEEL
Nominal Airflow: 500 cfm
Tilt Angle (Heating/Cooling): N/A Degrees
Pressure Drop: 0.60 inches
THERMAL EFFECTIVENESS RATINGS AT
0 in. PRESSURE DIFFERENTIAL
LEAKAGE RATINGS
LEGEND
62ECC AND 62E2C PERFORMANCE RATINGS
Type: WHEEL
Nominal Airflow: 1000 cfm
Tilt Angle (Heating/Cooling): N/A Degrees
Pressure Drop: 0.95 inches
THERMAL EFFECTIVENESS RATINGS AT
0 in. PRESSURE DIFFERENTIAL
LEAKAGE RATINGS
LEGEND
62ECD AND 62E2D PERFORMANCE RATINGS
Type: WHEEL
Nominal Airflow: 900 cfm
Tilt Angle (Heating/Cooling): N/A Degrees
Pressure Drop: 1.00 inches
THERMAL EFFECTIVENESS RATINGS AT
0 in. PRESSURE DIFFERENTIAL
LEAKAGE RATINGS
LEGEND
SENSIBLE LATENT TOTAL
100% Airflow Heating Condition: 71% 60% 67%
75% Airflow Heating Condition: 76% 67% 73%
100% Airflow Cooling Condition: 71% 60% 65%
75% Airflow Cooling Condition: 76% 67% 71%
TEST
PRESSURE
DIFFERENTIAL
EATR OACF
PURGE
ANGLE OR
SETTING
Test 1: –0.50 inches 7.7% 0.97 N/A
Test 2: 0.00 inches 0.4% 1.44 N/A
Test 3: 0.50 inches 0.0% 1.29 N/A
EATR — Exhaust Air Transfer Ratio
N/A — Not Applicable
OACF — Outdoor Air Correction Factor
SENSIBLE LATENT TOTAL
100% Airflow Heating Condition: 68% 60% 65%
75% Airflow Heating Condition: 73% 65% 70%
100% Airflow Cooling Condition: 68% 60% 64%
75% Airflow Cooling Condition: 73% 65% 69%
TEST
PRESSURE
DIFFERENTIAL
EATR OACF
PURGE
ANGLE OR
SETTING
Test 1: –0.50 inches 9.9% 1.02 N/A
Test 2: 0.00 inches 0.2% 1.33 N/A
Test 3: 0.50 inches 0.0% 1.59 N/A
EATR — Exhaust Air Transfer Ratio
N/A — Not Applicable
OACF — Outdoor Air Correction Factor
SENSIBLE LATENT TOTAL
100% Airflow Heating Condition: 70% 63% 68%
75% Airflow Heating Condition: 76% 70% 74%
100% Airflow Cooling Condition: 70% 63% 66%
75% Airflow Cooling Condition: 76% 70% 72%
TEST
PRESSURE
DIFFERENTIAL
EATR OACF
PURGE
ANGLE OR
SETTING
Test 1: –0.50 inches 4.8% 1.10 N/A
Test 2: 0.00 inches 0.2% 1.27 N/A
Test 3: 0.50 inches 0.0% 1.41 N/A
EATR — Exhaust Air Transfer Ratio
N/A — Not Applicable
OACF — Outdoor Air Correction Factor
SENSIBLE LATENT TOTAL
100% Airflow Heating Condition: 76% 68% 73%
75% Airflow Heating Condition: 81% 73% 78%
100% Airflow Cooling Condition: 76% 68% 72%
75% Airflow Cooling Condition: 81% 73% 76%
TEST
PRESSURE
DIFFERENTIAL
EATR OACF
PURGE
ANGLE OR
SETTING
Test 1: –1.00 inches 9.3% 0.97 N/A
Test 2: 0.00 inches 0.7% 1.19 N/A
Test 3: 1.00 inches 0.0% 1.34 N/A
EATR — Exhaust Air Transfer Ratio
N/A — Not Applicable
OACF — Outdoor Air Correction Factor
AHRI capacity ratings
Komentáře k této Příručce