CONFIGURING THE CONTROL SYSTEM
Configuring the
Comfort
Link™ Control (48/
50HG Units) The ComfortLink control must be config-
ured to use the enthalpy control. These configurations are
changed through the Scrolling Marquee display or a Carrier
Comfort Network device.
NOTE: Consult the Controls, Start-Up, Operation, Service and
Troubleshooting Instructions for in-depth instructions on using
and configuring the ComfortLink control. The following
instructions are written for the Scrolling Marquee display or
Navigator™ accessory.
1. The ComfortLink control must be configured to use the
economizer accessory. A password may be required to
edit the configurations depending on previous settings
configured in the unit. Default password is 1111.
2. To configure the ComfortLink control, use the arrow
keys to scroll the red LED on the display to the
“Configuration” position and press .
3. Use the arrow keys to scroll down until the display shows
“ECON”. This is the Economizer Configuration sub
menu. Press .
4. The control will display the Economizer Installed
(Configuration
ECON
EC.EQ)setting.Usethe
arrow keys to scroll down until the display shows
“EN.SW”. This is the enthalpy switch configuration.
Press once to select the Configuration
ECON
EN.SW setting for configuration. Press
again for “0” to begin flashing.
5. Use the arrow keys to change the configuration to “1” for
a normally open switch. The Carrier accessory and wiring
is shown for normally open. Change the configuration to
“2” if using a normally closed switch. Then press
and to save the setting.
6. For economizer cooling to occur, the enthalpy sensor
must sense “LOW” enthalpy and the outdoor-air temper-
ature (Temperatures
AIR.T
OAT), as measured by
the unit control sensor, must be lower than the Economiz-
er Cooling High Temperature Limit (ECL.H) and higher
than the Economizer Cooling Low Temperature Limit
(ECL.L). The values of ECL.H and ECL.L may be
viewed and changed in the Configuration
ECON
submenu.
7. If additional economizer control accessories have been
added or other configuration parameters are to be
changed from the factory defaults, then repeat the follow-
ing steps:
a. Use the arrow keys to scroll up or down to the
parameter to change. Press once to select
the setting for configuration.
b. Press again. The configuration value will
flash.
c. Use the arrow keys to change the configuration
value.
d. Press and to save the setting.
8. Configuration of the ComfortLink control is now com-
plete. Pressing multiple times will return the
display to the auto-scrolling setting.
9. The status of the enthalpy switch is accessible by viewing
the ENTH input located in the Input
SW.IN submenu.
10. Close and secure all access doors.
Configuring the
Comfort
Link Control 48/50PG
Units) —
The ComfortLink control must be configured to
use the enthalpy control. These configurations are changed
through the Scrolling Marquee display or a Carrier Comfort
Network device.
NOTE: Consult the Controls, Start-Up, Operation, Service and
Troubleshooting Instructions for in-depth instructions on using
and configuring the ComfortLink control. The following
instructions are written for the Scrolling Marquee display or
Navigator accessory.
1. The ComfortLink control must be configured to use the
economizer accessory. A password may be required to
edit the configurations depending on previous settings
configured in the unit. Default password is 1111.
2. To configure the ComfortLink control, use the arrow
keys to scroll the red LED on the display to the
“Configuration” position and press .
3. Use the arrow keys to scroll down until the display shows
“ECON”. This is the Economizer Configuration sub
menu. Press .
4. The control will display the Economizer Installed
(Configuration
ECON
EC.EN) setting. Use the
arrow keys to scroll down until the display shows
“EN.SW”. This is the enthalpy switch configuration.
Press once to select the Configuration
ECON
EN.SW setting for configuration. Press
again for “0” to begin flashing.
5. Use the arrow keys to change the configuration to “1” for
a normally open switch. The Carrier accessory and wiring
is shown for normally open. Change the configuration to
“2” if using a normally closed switch. Then press
and to save the setting.
6. For economizer cooling to occur, the enthalpy sensor
must sense “LOW” enthalpy and the outdoor-air temper-
ature (Te mperatures
AIR.T
OAT), as measured by
the unit control sensor, must be lower than the Economiz-
er Cooling High Temperature Limit (EH.LO) and higher
than the Economizer Cooling Low Temperature Limit
(EL.LO). The values of EH.LO and EL.LO may be
viewed and changed in the Configuration
ECON sub-
menu or in the Setpoints main menu.
7. If additional economizer control accessories have been
added or other configuration parameters are to be
changed from the factory defaults, then repeat the follow-
ing steps:
a. Use the arrow keys to scroll up or down to the
parameter to change. Press once to select
the setting for configuration.
b. Press again. The configuration value will
flash.
c. Use the arrow keys to change the configuration
value.
d. Press and to save the setting.
8. Configuration of the ComfortLink control is now com-
plete. Pressing multiple times will return the
display to the auto-scrolling setting.
9. The status of the enthalpy switch is accessible by viewing
the ENTH input located in the Input
GEN.I submenu
or the Run Status
ECON submenu.
10. Close and secure all access doors.
ENTER
ENTER
ENTER
ENTER
ENTER ESCAPE
ENTER
ENTER
ENTER ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER ESCAPE
ENTER
ENTER
ENTER ESCAPE
ESCAPE