Table 10 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
UNAUTHORIZED
OPERATION
UNIT SHOULD BE STOPPED CA P Emergency: Compressor run-
ning without control authorization.
Compressor is running with more than 10%
RLA and control is trying to shut it
down. Throw power off to compressor if
unable to stop. Determine cause before
repowering.
POTENTIAL FREEZE-UP EVAP PRESS/TEMP
TOO LOW
ERT Emergency: Freeze-up
prevention.
Determine cause. If pumping refrigerant
out of machine, stop operation and go over
pumpout procedures.
FAILURE TO STOP DISCONNECT POWER RUN AUX Emergency: DISCON-
NECT POWER.
Starter and run and start contacts are en-
ergized while control tried to shut down.
Disconnect power to starter.
LOSS OF
COMMUNICATION
WITH STARTER Loss of Communication with Starter:
Check machine.
Check wiring from PSIO to SMM. Check
SMM module troubleshooting procedures.
STARTER CONTACT
FAULT
ABNORMAL 1CR OR
RUN AUX
CR AUX Starter Contact Fault: Check
1CR/1M aux. contacts.
Starter run and start contacts energized
while machine was off. Disconnect power.
POTENTIAL FREEZE-UP COND PRESS/TEMP TOO LOW CRT Emergency: Freeze-up
prevention.
The condenser pressure transducer is read-
ing a pressure that could freeze the water
in the condenser tubes. Check for con-
denser refrigerant leaks, bad transduc-
ers, or transferred refrigerant. Place unit
in Pumpdown mode to eliminate ALARM
if vessel is evacuated.
H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RUNNING RESET ACTIVE 4-20MA SIGNAL
Reset program active based upon CONFIG table set-up.RUNNING RESET ACTIVE REMOTE SENSOR CONTROL
RUNNING RESET ACTIVE CHW TEMP DIFFERENCE
RUNNING TEMP CONTROL LEAVING CHILLED WATER Default method of temperature control.
RUNNING TEMP CONTROL ENTERING CHILLED WATER ECW control activated on CONFIG table.
RUNNING TEMP CONTROL TEMPERATURE RAMP LOADING Ramp loading in effect. Use Service1 table to modify.
RUNNING DEMAND LIMITED BY DEMAND RAMP LOADING Ramp loading in effect. Use Service1 table to modify.
RUNNING DEMAND LIMITED BY LOCAL DEMAND SETPOINT Demand limit set point is , actual demand.
RUNNING DEMAND LIMITED BY 4-20MA SIGNAL
Demand limit is active based on CONFIG table set-up.RUNNING DEMAND LIMITED BY CCN SIGNAL
RUNNING DEMAND LIMITED BY LOADSHED/REDLINE
RUNNING TEMP CONTROL HOT GAS BYPASS
Hot Gas Bypass is energized. See surge prevention in the
control section.
RUNNING DEMAND LIMITED BY LOCAL SIGNAL Active demand limit manually overridden or Status01 table.
RUNNING TEMP CONTROL ICE BUILD Machine in Ice Build temperature control.
73