Carrier 17/19EX Specifikace Strana 340

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 437
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 339
Legend
FLA Full Load Amps
LRA Locked Rotor Amps
Notes:
1. The oil pump is powered through a field wiring terminal into the power panel.
2. Power to the controls and oil heater via the power panel must be on circuits that can provide continuous
service when the compressor starter is disconnected.
Table 16 — Auxiliary Systems, Electrical Data
Power Source Item Supply V-PH-HZ FLA LRA
1
Control Module and
Actuator
115-1-60
115-1-50
3.50
Oil Sump Heater 115-1-60
115-1-50
8.70
2
Oil Pump 200/240-3-60
380/480-3-60
507/619-3-60
4.32
2.15
2.13
24.5
12.2
25.0
220/240-3-50
346/440-3-50
4.83
2.59
28.0
12.2
3 (Optional)
Pumpout Compressor 200/208-3-60
220/240-3-60
440/480-3-60
550/600-3-60
10.9
9.50
4.70
3.80
63.5
57.5
28.8
23.0
380/415-3-50 4.70 28.8
Zobrazit stránku 339