IM 358-6 / Page 1 (Rev. 9/99)Group: PTACPart No.: 106018431Date: September 1999Installation & Maintenance DataIM 358-6Type K Incremental Packag
IM 358-6 / Page 10 (Rev. 9/99)Units With Hydronic Heat (Sizes 007–014)The hydronic heat section can be supplied with a short (41⁄4''high) co
IM 358-6 / Page 11 (Rev. 9/99)Unit with Hydronic Heat (sizes 019–022)1. Only one size control box is available for sizes 019–022.Make all electrical c
IM 358-6 / Page 12 (Rev. 9/99)4. Fasten the two (2) end plates to the room cabinet usingthe wing nuts supplied. These end plates are adjustableand sho
IM 358-6 / Page 13 (Rev. 9/99)Equipment Start-upManual Changeover Thermostat Automatic Changeover ThermostatThermostat Part # 0046736101 Thermostat Pa
IM 358-6 / Page 14 (Rev. 9/99)Typical Wiring DiagramsStandard Chassis With Electric Heat & MCO Controls (Sizes 007—014)C1 Capacitor, Indoor FanC2
IM 358-6 / Page 15 (Rev. 9/99)Standard Chassis With Electric Heat & MCO Controls (Sizes 019—022)Note: Large heat shown. Refer to unit diagram ford
IM 358-6 / Page 16 (Rev. 9/99)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor FanC3 Capacitor, CompressorGRC Guest Room ControlHL High LimitHTR HeaterMP
IM 358-6 / Page 17 (Rev. 9/99)Standard Chassis With Hot Water & MCO Controls (Sizes 019—022)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor FanC3 Ca
IM 358-6 / Page 18 (Rev. 9/99)Standard Chassis With Steam Heat & MCO Controls (Sizes 007—014)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor FanC3 C
IM 358-6 / Page 19 (Rev. 9/99)Standard Chassis With Steam Heat & MCO Controls (Sizes 019—022)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor FanC3 C
IM 358-6 / Page 2 (Rev. 9/99)Table of ContentsFigure 1.When the equipment is received, all items should be carefullychecked against the bill of lading
IM 358-6 / Page 20 (Rev. 9/99)Standard Chassis With Electric Heat & 24V Wall Stat (Sizes 007—014)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor Fan
IM 358-6 / Page 21 (Rev. 9/99)Standard Chassis With Hot Water Heat & 24V Wall Stat (Sizes 007—014)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor Fa
IM 358-6 / Page 22 (Rev. 9/99)Standard Chassis With Steam Heat & 24V Wall Stat (Sizes 007—014)C1 Capacitor, Indoor FanC2 Capacitor, Outdoor FanC3
IM 358-6 / Page 23 (Rev. 9/99)Scheduled MaintenanceRecommended Spare PartsAn advantage of the Incremental system is that failure of anyone part affect
IM 358-6 / Page 24 (Rev. 9/99)Troubleshooting ChartThese items should be checked by a qualified service technician only.TROUBLE CAUSE CURE1. Blowers w
IM 358-6 / Page 25 (Rev. 9/99)Troubleshooting Chart (cont'd)These items should be checked by a qualified service technician only.TROUBLE CAUSE CU
IM 358-6 / Page 26 (Rev. 9/99)Approximate Shipping WeightsCooling ChassisSize 007 ...
IM 358-6 / Page 27 (Rev. 9/99)NOTES
AAF–McQuay Incorporated4900 Technology Park Boulevard, Auburn, New York 13021-9030 USA (315) 253-2771Printed on recycled paper containing at least 10%
IM 358-6 / Page 3 (Rev. 9/99)TYPE K CHASSISPKES1009CZ00Z00AR14C1B 1Product Category Product StyleP= Type K Incremental 1= 1st Tyle ChangeProduct Ident
IM 358-6 / Page 4 (Rev. 9/99)Table 2.Dimensions — inchesWall Box 007— 014 21⁄2 31⁄2 45678910“B” Dimension 019 — 022 21⁄2 31⁄2 41⁄2 51⁄2 61⁄2 71⁄2 81⁄
IM 358-6 / Page 5 (Rev. 9/99)Outdoor Louver Installation1. Remove the louver from the shipping carton which alsocontains the mounting hardware.2. Remo
IM 358-6 / Page 6 (Rev. 9/99)Additional Instructions for Hydronic Heat (Sizes 007–014)6. The piping for steam or hot water can be supplied fromeither
IM 358-6 / Page 7 (Rev. 9/99)Heat Section Installation (Sizes 019–022)Figure 7 shows the heat section installed in a standard wallbox. Note that the h
IM 358-6 / Page 8 (Rev. 9/99)Figure 12.1. Remove the cooling chassis from the shipping carton andexamine it for damage. Do not rest it on end. Check
IM 358-6 / Page 9 (Rev. 9/99)Electric Power WiringFigure 13. Electric Heat Section (Sizes 007–014)Before making any electrical connections, observe th