50TC
Single Package Rooftop, 50Hz
Cooling Only
S i z e s 0 7 --- 1 4
with Puronr (R---410A) Refrigerant
Installation Instructions
NOTE: This manual discusses only the mechanical
installation of this unit. Star--up procedures, operating
sequences and service instructions are included in a
separate Service/Maintenance manual which is not
included with this unit. Other manuals may be required
for specific factory--installed options.
Read through the entire installation instruction manual
before starting the installation, to familiarize yourself with
all steps and to identify additional reference materials
required.
Contact your local Carrier representative for additional
service reference materials.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
INSTALLATION 6...............................
Step 1 -- Plan for Unit Location 6..................
Step 2 -- Plan for Sequence of Unit Installation 7......
Step 3 -- Inspect Unit 7...........................
Step 4 -- Provide Unit Support 7...................
Step 5 -- Field Fabricate Ductwork 10...............
Step 6 -- Rig and Place Unit 11....................
Step 7 -- Convert to Horizontal & Connect Ductwork 11
Step 8 -- Install Outside Air Hood 11...............
Step 9 -- Install External Condensate Trap and Line 13.
Step 10 -- Make Electrical Connections 13...........
Step 11 -- Adjust Factory--Installed Options 35........
Step 12 -- Install Accessories 35...................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes for special
requirements. In absence of local codes, it is
recommended that the USA standard ANSI/NFPA 70,
National Electrical Code (NEC), be followed.
It is important to recognize safety information. This is the
safety--alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Zobrazit stránku 0
1 2 3 4 5 6 ... 39 40

Shrnutí obsahu

Strany 1 - Installation Instructions

50TCSingle Package Rooftop, 50HzCooling OnlyS i z e s 0 7 --- 1 4with Puronr (R---410A) RefrigerantInstallation InstructionsNOTE: This manual discusse

Strany 2

10CONNECTORPKG. ACCY.BCD ALTDRAINHOLEPOWER CONTROLACCESSORYPOWERCRBTMPWR003A011’-911/16”[551]13/4”[44.5]1’-4”[406]CRBTMPWR004A013/4” [19] NPT11/4” [

Strany 3

1150TC-*0850TC-*08 – – 1414UNIT SIZEROOFCURBACCESSORYCRRFCURB003A01CRRFCURB004A011’ - 2”[356]2’ - 0”[610]C09453Fig.6--RoofCurbDetails–08—14SizeUnits5

Strany 4

12A-B0.5” (13)B-C1.0” (25)A-C1.0” (25)MAXIMUM ALLOWABLEDIFFERENCE IN. (MM)C06110Fig. 7 -- Unit Leveling TolerancesStep 5 — Field Fabricate DuctworkPRO

Strany 5

13Step 6 — Rig and Place UnitWhen the unit (50TC--D08, 50TC--D09, or 50TC--D12 only)is ready to be rigged and no longer will be lifted by a forktruck,

Strany 6

14EconomizerCut Plastic Ties(2) PlacesRemove Hood PartsC08633Fig. 11 -- Economizer Parts, Shipping LocationTwo Position Damper Hood Removal and Setup

Strany 7

155. Open the filter clips which are located underneath thehood top. Insert the aluminum filter into the bottomfilter rack (hood divider). Push the fi

Strany 8 - INSTALLATION

16The unit is factory wired for the voltage shown on ;thenameplate. Refer to the unit label diagram for additionalinformation.!WARNINGFIRE HAZARDFailu

Strany 9 - Step 4 — Provide Unit Support

17Check tightness of connector lock nuts before connectingelectrical conduits.Field--supplied and field--installed liquidtight conduitconnectors and c

Strany 10

18Table 3 – Heater Model NumberBare H eater Model Number C R H E A T E R 0 1 6 A 0 0Heater Sales Package PNOIncludes:Bare H eaterCarton and packing ma

Strany 11

19TRACKFLANGEC08135Fig. 25 -- Typical Module InstallationSingle Point Boxes and Supplementary Fuses — Whenthe unit MOCP device value exceeds 60--A, un

Strany 12 - DETAIL “A”

2ELECTRICAL SHOCK HAZARDFailure to follow this warning could cause personalinjury or death.Before performing service or maintenance operationson unit,

Strany 13 - INDOOR COIL ACCESS PANEL

20PremierLinkt (Factory--Option) —C08199Fig. 28 -- PremierLink ControllerThe PremierLink controller (see Fig. 28) is compatiblewith Carrier Comfort Ne

Strany 14 - Remove Hood Parts

21C09460Fig. 30 -- PremierLink Wiring Schematic50TC

Strany 15

22Outdoor Air Temperature (OAT) Sensor — The OAT isfactory--mounted in the EconoMi$er2 (FIOP oraccessory). It is a nominal 10k ohm thermistor attached

Strany 16 - Units With Disconnect Option

23Table 5 – Space Sensor ModeTB1 TERMINAL FIELD CONNECTION INPUT SIGNAL1 T 5 5 --- S E N / T 5 6 --- S E N Analog (10k thermistor)2 RMTOCC Discrete, 2

Strany 17 - Connections

24234561SW1SENBRN (GND)BLU (SPT)RED(+)WHT(GND)BLK(-)CCN COMSENSOR WIRINGC08201Fig. 31 -- T--55 Space Temperature Sensor WiringConnect T--55 -- See Fig

Strany 18 - Electric Heaters

25When the PremierLink is configured for ThermostatMode, these functions are not available: Fire Shutdown(FSD), Remote Occupied (RMTOCC), Compressor S

Strany 19

268765432121HG24 VACOR24 VDCNCALARMRELAYCONTACTSCOMNO}0-10VDCSIG COM4-20mA++-+-J3 J4C08635Fig. 38 -- Indoor/Outdoor Air Quality (CO2)Sensor(33ZCSENCO2

Strany 20

27PremierLink control can monitor return filter status in twoways: By monitoring a field--supplied/installed filterpressure switch or via supply fan r

Strany 21

28NOTE: Conductors and drain wire must be at least 20AWG, stranded, and tinned copper. Individual conductorsmust be insulated with PVC, PVC/nylon, vin

Strany 22

29RTU--MP control systemThe RTU--MP controller, see Fig. 46, provides expandedstand--alone operation of the HVAC system plusconnection and control thr

Strany 23

3Horizontal Connections / EconomizerVertical Connections / EconomizerC09447Fig. 1 -- Unit Dimensional Drawing – 07 Size Units50TC

Strany 24 - Cool Warm

30C09461Fig. 48 -- RTU--MP System Control Wiring Diagram50TC

Strany 25

31Table 9 – RTU--MP Controller Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBERSINPUTSSpace Temperature Sensor sptsens AI

Strany 26 - COVER REMOVED SIDE VIEW

32Field Connections -- Field connections for accessorysensors and input devices are made the RTU--MP, at plugsJ1, J2, J4, J5, J11 and J20. All field c

Strany 27

33To wire the return air enthalpy sensor, perform thefollowing:1. Use a 2--conductor, 18 or 20 AWG, twisted pair cableto connect the return air enthal

Strany 28

34Fan StatusThe fan status accessory is a field--installed accessory.This accessory detects when the indoor fan is blowing air.When installing this ac

Strany 29 - RTU-MP Board

35Local AccessBACview6HandheldThe BACview6is a keypad/display interface used toconnect to the RTU--MP to access the control information,read sensor va

Strany 30

36Table 10 – LEDsThe LEDs on the RTU--MP show the status of certain functionsIf this LED is on... Status is...Power The RTU MP has powerRx The RTU MP

Strany 31

37Economizer 2 PositionDamperUnit Without Economizeror 2 Position DamperPowerExhaustC09382Fig. 56 -- EconoMi$ert IV WiringStep 11 — Adjust Factory--In

Strany 32

38Table 11 – Unit Wire/MOCP Sizing DataUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERCRHEATER***A00Nom(kW)FLA MCAFUSE orHARCBRKRDISC. SIZEFLA LRA

Strany 33 - Connecting Discrete Inputs

39Table 11 – Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERCRHEATER***A00Nom(kW)FLA MCAFUSE orHARCBRKRDISC. SIZE

Strany 34 - Remote Occupancy

4C09448Fig. 1 -- Unit Dimensional Drawing – 07 Size Unit (cont.)50TC

Strany 35 - Communication

40Table 11 – Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERCRHEATER***A00Nom(kW)FLA MCAFUSE orHARCBRKRDISC. SIZE

Strany 36

5Horizontal Connections / EconomizerVertical Connections / EconomizerC09450Fig. 2 -- Unit Dimensional Drawing – 08, 09 and 12 Size Units50TC

Strany 37 - Pre--Start and Start--Up

6C09451Fig. 2 -- Unit Dimensional Drawing – 08, 09 and 12 Size Units (cont.)50TC

Strany 38

7Vertical Connections / EconomizerHorizontal Connections / EconomizerC10407Fig. 3 -- Unit Dimensional Drawing – 14 Size Units50TC

Strany 39

8C10408Fig. 3 -- Unit Dimensional Drawing – 14 Size Units (cont.)INSTALLATIONJobsite SurveyComplete the following checks before installation.1. Consul

Strany 40 - Legend for Table 11

9Table 1 – Operating Weights50TC--- UNITS KG (LB)Component A07 D08 D09 D12 D14Base Unit 277 (610) 340.5 (750) 388.2 (855) 392.7 (865) 467 (1030)Econom