38TDBWeatherMaker™ Two-SpeedAir Conditioning Unit with Puron®Installation and Start-Up InstructionsNOTE: Read the entire instruction manual before sta
Step 10—Start-UpTo prevent compressor damage or personal injury, observethe following:• Do not overcharge system with refrigerant.• Do not operate uni
Step 11—Check ChargeService valve gage ports are not equipped with Schradervalves. To prevent personal injury, make sure gage manifoldis connected to
FACTORY DEFAULTSFactory defaults have been provided in the event of failure ofoutdoor air thermistor, coil thermistor, and/or furnace interfacejumper.
Compressor Control ContactorsLow and high capacity contactor coils are 24 volts. The electroniccontrol board controls the operation of the low speed (
Fig. 15—Wiring Diagram—024, 036, 048A01513CONNECTION DIAGRAMOCT-t°LPSHPSOAT-t°LOHITO INDOOR UNITREDCCHFAN CAPYELREDBRNOFMBLKBLU/PNKBLU/PNKYEL/PNKYEL/P
Fig. 16—Wiring Diagram—037A01439CONNECTION DIAGRAMOCT-t°LPSHPSOAT-t°LOHITO INDOOR UNITCCHREDBRNBLU/PNKBLU/PNKYEL/PNKYEL/PNKBRNBRNBLKBLKREDBLUCH1121232
→ Fig. 17—Wiring Diagram—060A02212CONNECTION DIAGRAMOCT-t∞LPSHPSOAT-t∞LOHITO INDOOR UNITREDCCHFA N CAPREDBRNOFMBLKBLU/PNKBLU/PNKYEL/PNKYEL/PNKBRNBRNBL
INSPECT EQUIPMENTFile claim with shipping company prior to installation if shipmentis damaged or incomplete.Step 2—Install on a Solid, Level Mounting
8. Install vapor elbow (see Fig. 5B) with equalizer adapter tosuction tube of line set and suction connection to indoor coil.Adapter has a 1/4-in. mal
Do not leave system open to atmosphere any longer thanminimum required for installation. POE oil in compressor isextremely susceptible to moisture abs
5. Repeat this procedure as indicated in Fig. 9. System will thencontain minimal amounts of contaminants and water vapor.FINAL TUBING CHECKIMPORTANT:
O/W2W/W1Y1/W2GRTHERMIDISTATCONTROLMODEL RHVARIABLE-SPEEDCONDENSINGFURNACETWO-SPEEDAIR CONDITIONERW/W1GY/Y2CY2RY1CDHUMHUMBS1S2W2RCHEAT STAGE 1COOL STAG
COOL STAGE 1FANHEAT STAGE 1COOL STAGE 2N/A24 VAC HOTRW/W1Y/Y2O/W2Y1/W2G24 VAC COMMN/AOUTDOORSENSORCONNECTIONCBS1S2CY2CPROGRAMMABLETHERMOSTATMODEL 2SSI
required. The LCC for standard PSC blower products consists of astandard humidistat which opens contacts on humidity rise and apilot duty relay with 2
A01222LEGEND24 VOLT FACTORY WIRING24 VOLT FIELD WIRINGFIELD SPLICE CONNECTIONRELAY SPDT, PILOT DUTY24-V COIL (HN61KK324)OR EQUIVALENTHUMIDISTAT, OPENS