48HC
Single Package Rooftop
Gas Heating/Electric Cooling Unit
with Puronr (R---410A) Refrigerant
Sizes: 17, 20, 24, 28
Installation Instructions
NOTE: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
INSTALLATION 9...............................
Jobsite Survey 9................................
Step 1 -- Plan for Unit Location 9..................
Roof Mount 9...............................
Step 2 -- Plan for Sequence of Unit Installation 10.....
Curb--Mount Installation 10....................
Pad--Mount Installation 10.....................
Frame--Mount Installation 10...................
Step 3 -- Inspect Unit 10..........................
Step 4 -- Provide Unit Support 10..................
Roof Curb Mount 10.........................
Slab Mount (Horizontal Units Only) 10..........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 10.............
Step 5 -- Field Fabricate Ductwork 14...............
Step 6 -- Rig and Place Unit 14....................
Positioning on Curb 15.......................
Step 7 -- Horizontal Duct Connection 15............
Step 8 -- Install Outside Air Hood — Factory Option 15..
Step 9 -- Install Flue Hood and Combustion Air Hood 16..
Step 10 -- Install Gas Piping 16....................
Gas Supply Line 16..........................
Factory--Option Thru--Base Connections 18.......
Step 11 -- Install External Condensate Trap and Line 19..
Step 12 -- Make Electrical Connections 19...........
Field Power Supply 19........................
Units without Factory--Installed Disconnect 20....
Units with Factory--Installed Disconnect 20.......
All Units 20................................
Convenience Outlets 20.......................
Factory--Option Thru--Base Connections 22......
Units without Thru--Base Connections 22.........
Field Control Wiring 22.......................
Thermostat 22...............................
Unit without Thru--Base Conversion Kit 22.......
Heat Anticipator Settings 23...................
Transformer Connection
for 208--v Power Supply 23.....................
Humidi--MiZer
R
Control Connections 24..........
Humidi--MiZer -- Space RH Controller 24........
PremierLinkt (Factory Option) 26...............
Supply Air Temperature (SAT) Sensor 29.........
Outdoor Air Temperature (OAT) Sensor 29.......
EconoMi$er2 29.............................
Field Connections 29..........................
Space Sensors 31............................
Connect Thermostat 31.......................
Configure the Unit for Thermostat Mode 31......
Economizer Controls 32........................
Indoor Air Quality (CO
2
)Sensor 32.............
Outdoor Air Quality Sensor 32.................
Space Relative Humidity Sensor or
Humidistat Connections 33....................
Smoke Detector/Fire Shutdown (FSD) 34.........
Filter Status Switch 34........................
Supply Fan Status Switch 34...................
Remote Occupied Switch 34...................
Power Exhaust (output) 34.....................
CCN Communication Bus 35..................
RTU Open Control System 36...................
Supply Air Temperature (SAT) Sensor 39.........
Outdoor Air Temperature (OAT) Sensor 39.......
EconoMi$er2 39.............................
Zobrazit stránku 0
1 2 3 4 5 6 ... 51 52

Shrnutí obsahu

Strany 1 - Installation Instructions

48HCSingle Package RooftopGas Heating/Electric Cooling Unitwith Puronr (R---410A) RefrigerantSizes: 17, 20, 24, 28Installation InstructionsNOTE: Read

Strany 2

10Step 2 — Plan for Sequence of Unit InstallationThe support method used for this unit will dictate differentsequences for the steps of unit installat

Strany 3

11C10954Fig. 6 -- Roof Curb Details – 17 Size Unit48HC

Strany 4

12C10955Fig. 7 -- Roof Curb Details – 20 and 24 Size Units48HC

Strany 5

13C10956Fig. 8 -- Roof Curb Details – 28 Size Unit48HC

Strany 6

14A-B0.25” (6)B-C0.5” (12)A-C0.5” (12)MAXIMUM ALLOWABLEDIFFERENCE IN. (MM)ABCC10628Fig. 9 -- Unit Leveling TolerancesStep 5 — Field Fabricate Ductwork

Strany 7

15PositioningonCurb—Position unit on roof curb so that the following clearancesare maintained:1/4in. (6 mm) clearance between the roofcurb and the bas

Strany 8

16To assemble the outside air hood:1. Remove hood top panel from shipping position onunit end.2. Install four angles to the upper end panel using thes

Strany 9 - INSTALLATION

17Table 2 – Typical3/4--in NPT Field Supplied Piping PartsItem Qty CPN Description1 1 CA15RA201 90 Deg Street Elbow2 1 CA01CA226 5 Inch Long Nipple3 1

Strany 10 - Step 4 — Provide Unit Support

18Factory--Option Thru--Base Connections —Electrical Connections: Knockouts are located in thecontrol box area. Remove the appropriate size knockoutfo

Strany 11

19Step 11 — Install External Condensate Trap andLineThe unit has one3/4-in. condensate drain connection onthe end of the condensate pan (see Fig. 21).

Strany 12

2Field Connections 39...Space Temperature (SPT) Sensors 40...Indoor Air Quality (CO2)Sensor 40...Outdoor Air

Strany 13

20FIRE HAZARDFailure to follow this warning could result inintermittent operation or unsatisfactory performance.Do not connect aluminum wire between d

Strany 14 - DETAIL A

21Two types of convenience outlets are offered on 48HCmodels: Non--unit powered and unit--powered. Both typesprovide a 125--volt GFCI (ground--fault c

Strany 15 - Position

222.050HE501288NOTICE/AVISConvenience Outlet UtilizationMaximum Intermittent Use 15 - AmpsMaximum Continuous Use 8 - AmpsObserve a 50% limit on the

Strany 16 - Step 10 — Install Gas Piping

23CW2GW1RY1 TypicalThermostatCorrectionsO/B/Y2(see Note)Note: Typical multi-function marking. Follow manufacturer’s configuration instructions t

Strany 17

24Humidi--MiZerRControl ConnectionsHumidi--MiZer – Space RH Controller —NOTE: The Humidi--MiZer is a factory installed option.The Humidi--MiZer dehumi

Strany 18

25C11139Fig. 34 -- Typical Humidi--MiZerRAdaptive Dehumidification System Humidistat WiringRcRhW1GY2CO/W2/BY1OATRRSSRTNHUMD1D2V+VgX*CGW2W1Y2Y1REDGE Pr

Strany 19 - CONNECTION

26PremierLinkt (Factory--Option)C08199Fig. 36 -- PremierLink ControllerThe PremierLink controller (see Fig. 36) is compatiblewith Carrier Comfort Netw

Strany 20 - Units With Disconnect Option

27C11140Fig. 38 -- PremierLink Wiring Schematic48HC

Strany 21

28C11141Fig. 39 -- PremierLink Wiring Schematic with Humidi--MiZerR48HC

Strany 22 - NOTICE/AVIS

29Supply Air Temperature (SAT) Sensor —On FIOP--equipped 48HC unit, the unit is supplied with asupply--air temperature (SAT) sensor (33ZCSENSAT).This

Strany 23 - Field Wiring

3C10896Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit48HC

Strany 24 - Control Connections

30Table 5 – Space Sensor ModeTB3 TERMINAL FIELD CONNECTION INPUT SIGNAL1 T 5 5 --- S E N / T 5 6 --- S E N Analog (10k thermistor)2 RMTOCC Discrete, 2

Strany 25 - THERMOSTAT

31Space Sensors —The PremierLink controller is factory--shipped configuredfor Space Sensor Mode. A Carrier T--55 or T--56 spacesensor must be used. T-

Strany 26

32Economizer ControlsIndoor Air Quality (CO2)Sensor—The indoor air quality sensor accessory monitors spacecarbon dioxide (CO2) levels. This informatio

Strany 27

33J5-2J5-31311TB3TB3OAQ SensorPL24 VAC4-20mASIG COMC11157Fig. 49 -- Outdoor CO2Sensor ConnectionsSpace Relative Humidity Sensor or HumidistatConnectio

Strany 28

34Smoke Detector/Fire Shutdown (FSD) —This function is available only when PremierLink isconfigured for (Space) Sensor Mode. The unit isfactory--wired

Strany 29 - Field Connections

35CCN Communication Bus —The PremierLink controller connects to the bus in a daisychain arrangement. Negative pins on each componentmust be connected

Strany 30 - Table 6 – Thermostat Mode

36RTU Open Control SystemThe RTU Open control is factory--mounted in the 48HCunit’s main control box, to the right of the CTB. SeeFig. 37. Factory wir

Strany 31 - Cool Warm

37C11142Fig. 58 -- RTU Open System Control Wiring Diagram48HC

Strany 32 - Economizer Controls

38C11143Fig. 59 -- RTU Open System Control Wiring Diagram with Humidi--MiZerR48HC

Strany 33 - Io VoVin Gnd

39Table 9 – RTU Open Controller Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBER(S)DEDICATED INPUTSSpace Temp / Zone Temp

Strany 34

4C10897Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit (cont.)48HC

Strany 35

40to the RTU Open. Connect to the wires to the removablePhoenix connectors and then reconnect the connectors tothe board.Space Temperature (SPT) Senso

Strany 36 - RTU Open Control System

41isolated 24 vac power source to the sensor and to connectthe sensor to the control board terminals.To connect the sensor to the control, identify th

Strany 37

42Relative Humidity Sensor(Polarized Male Connector)J4-1 or J4-4 + 24 VDC Supply VoltageJ4-2 or J4-5 (-) 4 to 20 mA Current Loop Outputto RTU-OPEN4-20

Strany 38

43Communication Wiring -- ProtocolsGeneral —Protocols are the communication languages spoken bycontrol devices. The main purpose of a protocol is toco

Strany 39

44Local Access —BACview6Handheld: The BACview6is a keypad/displayinterface used to connect to the RTU Open to access thecontrol information, read sens

Strany 40

45Table 10 – LEDsThe LEDs on the RTU Open Control Board (see Fig. 57) show the status of certain functions:If this LED is on... Status is...Power RTU

Strany 41

46GRABLKRED– 4-20 Main+ VDC Out– 4-20 Main Out+ 24-36 VDC InLOWGND24V7PL6-1 (24-V)PL6-4 (COM)Outside AirEnthalpy SwitchReturn AirEnthalpySens

Strany 42 - (Polarized Male Connector)

47To install the return air sensor sampling tube:1. Remove the tube from its shipping location.2. Open the unit end to access the return air sensor (l

Strany 43 - Baud Rate Selections

48Table 11 -- Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNOM.V --- P h --- H zIFMTYPECOMBUSTI ONF AN MOTORPOWEREXHAUSTw/ PWRD C.O.NO P.E. w/

Strany 44 - Protocol Selector

49Legend and Notes for Table 11LEGEND:BRKR --- Circuit breakerCO --- C onvenience outletDISC --- DisconnectFLA --- Full load ampsLRA --- Locked rotor

Strany 45 - 33CSENTHSW)

5C10892Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units48HC

Strany 46 - Smoke Detectors

50Economizer 2 Position DamperUnit Without Economizer or2 Position DamperC10645Fig. 76 -- EconoMi$ert IV WiringStep 13 — Adjust Factory--Installed Opt

Strany 48

52Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/11Manufacturer r es er ves the right t

Strany 49 - Legend and Notes for Table 11

6C10893Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units (cont.)48HC

Strany 50 - Step 14 — Install Accessories

7C10900Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit48HC

Strany 51

8C10901Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit (cont.)48HC

Strany 52 - Catalog No: 48HC---11SI

9INSTALLATIONJobsite SurveyComplete the following checks before installation.1. Consult local building codes and the NEC (NationalElectrical Code) ANS