Carrier 59SC2A Manuál s instrukcemi

Procházejte online nebo si stáhněte Manuál s instrukcemi pro ne Carrier 59SC2A. Carrier 59SC2A Instruction manual [en] Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 84
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
1
59SC2A
Single Stage 4---Way Multipoise
Condensing Gas Furnace
Series 100
Installation, Start---up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS 3.........................
INTRODUCTION 4...................................
CODES AND STANDARDS 4...........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 4...
ACCESSORIES 5.....................................
LOCATION 8........................................
General 8.........................................
AIR FOR COMBUSTION AND VENTILATION 9..........
Introduction 9.....................................
CONDENSATE TRAP 13...............................
Upflow 13........................................
Downflow 13.....................................
Horizontal 13.....................................
CONDENSATE DRAIN 17.............................
INSTALLATION 20...................................
Upflow 20........................................
Downflow 20.....................................
Horizontal 21......................................
Filter Arrangement 21...............................
AIR DUCTS 29.......................................
General Requirements 29.............................
Ductwork Acoustical Treatment 29.....................
GAS PIPING 31......................................
ELECTRICAL CONNECTIONS 32.......................
115--V Wiring 32...................................
J--Box Installation 33................................
24--V Wiring 33....................................
Accessories 33.....................................
Alternate Power Supplies 33..........................
VENTING 37........................................
Special Venting Requirements for Installations in Canada 37.
General 38........................................
Materials 38.......................................
Venting Systems 38.................................
Locating the Vent Termination 39......................
Combustion Air and Vent Piping Insulation Guidelines 41...
START--UP, ADJUSTMENT, AND SAFETY CHECK 62......
General 62.........................................
Prime Condensate Trap 62.............................
Purge Gas Lines 62...................................
Adjustments 62......................................
SERVICE AND MAINTENANCE PROCEDURES 70........
Cleaning Heat Exchangers 75...........................
SEQUENCE OF OPERATION 79........................
PARTS REPLACEMENT GUIDE 83......................
TABLES
Loose Parts Bag 5.....................................
Minimum Clearances to Combustible Materials 5.............
Minimum Free Area Required 11.........................
Minimum Space Volumes 11.............................
Filter Size Information 24...............................
Opening Dimensions 25................................
Air Delivery CFM 30...................................
Maximum Capacity of Pipe 32...........................
Electrical Data 34......................................
Vent Termination Kit for Direct Vent (2--Pipe) System 39.......
Combustion--Air Vent Pipe, Fitting & Cement Material.. 45.....
Maximum Allowable Exposed Vent Lengths Insulation 46......
Maximum Equivalent Vent Length 47......................
Deductions from Maximum Equivalent Vent Length 47........
Blower Off Delay Setup Switch 64........................
Altitude Derate Multiplier for U.S.A. 65....................
Gas Rate 67..........................................
Orifice Size and Manifold Pressure 68.....................
CERTIFIED
Use of the AHRI Certified
TM
Mark indicates a
manufacturers participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2009E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the complete
and official position of the NFPA or ANSI on the referenced
subject, which is represented only by the standard in its entirety.
Zobrazit stránku 0
1 2 3 4 5 6 ... 83 84

Shrnutí obsahu

Strany 1 - Series 100

159SC2ASingle Stage 4---Way MultipoiseCondensing Gas FurnaceSeries 100Installation, Start---up, Operating andService and Maintenance InstructionsNOTE:

Strany 2 - IMPORTANT

10The opening shall commence within 12 in. (300 mm) of theceiling. Appliances in the space shall have clearances of at least 1in. (25 mm) from the sid

Strany 3 - SAFETY CONSIDERATIONS

11Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to OutdoorsFURNACEINPUT(BTUH)TWO HORIZONTAL DUCTS(1 SQ. IN./2,000 BTUH)

Strany 4 - PRECAUTIONS PROCEDURE

12*Minimum dimensions of 3‐in. (76mm)NOTE: Use any of the following combinations of openings: A & B, C & D, D & E, F & GL12F01

Strany 5 - ACCESSORIES

13CONDENSATE TRAPCondensate Trap -- Upflow OrientationWhen the furnace is installed in the upflow position, it is notnecessary to relocate the condens

Strany 6 - Fig. 1 -- Dimensional Drawing

14Remove relief tube from reliefport on condensate trap.Remove the screwthat secures the trap to the collector box andremove trap.Loosen clamp on inle

Strany 7 - 80 / 27˚C

15Remove plug fromcollector box.DO NOT DISCARD.If alternate vent positionis required, loosen clampon inlet of vent elbow.Remove the screw that secures

Strany 8 - LOCATION

16If alternate vent positionis required, loosen clampon vent elbow inlet.Remove relief tubefrom port on collectorbox.Remove the screw that secures the

Strany 9 - VENTILATION

17CONDENSATE DRAIN CONNECTIONFROZEN AND BURST WATER PIPE HAZARDFailure to protect against the risk of freezing may result inproperty damage.Special pr

Strany 10 - Standard Method

18the other side of the casing should be facing the front of thefurnace.11. Slide a spring clamp over the end of the remaining rubberdrain elbow.12. A

Strany 11 - NP = Not Permitted

19INSTALL CLAMPS ON DRAIN TUBEATTACH DRAIN TUBE TO CONDENSATE DRAIN TRAPPULL DRAIN STUB THROUGH CASINGOPEN SPRING CLAMPINSERT FACTORYïSUPPLIED 1/2ïIN.

Strany 12 - Outdoors

2Required Notice for Massachusetts InstallationsIMPORTANTThe Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:5.08

Strany 13 - CONDENSATE TRAP

20INSTALLATIONThis furnace is certified to leak 2% or less of nominal airconditioning CFM delivered when pressurized to 1--in. watercolumn with all pr

Strany 14 - Downflow Trap Configuration

21Return Air ConnectionsFIRE HAZARDA failure to follow this warning could cause personal injury,death and/or property damage.Never connect return--air

Strany 15 - (Appearance may vary)

22There are no provisions for an internal filter rack in these furnaces.An external filter is required and is purchased separately. A fieldsupplied ac

Strany 16

23Table 5 – Filter Media Pressure Drop (Clean) Versus Airflow -- In. W.C. (Pa)14 x 25 Filter(356 x 635 mm)Factory-AccessoryWashableFactory-AccessoryMe

Strany 17 - CONDENSATE DRAIN CONNECTION

24Table 7 – Air Filter Selection and Duct Sizing -- In. (mm)FURNACE CASING WIDTHFILTER SIZEFILTER TYPESIDERETURNBOTTOMRETURN14---3/16{ (360)16 x 25 x

Strany 18 - L12F019B

25PLENUMOPENINGCABDFLOOROPENINGDOWNFLOWSUBBASESHEET METALPLENUMFLOOROPENINGFURNACE(OR COIL CASINGWHEN USED)COMBUSTIBLEFLOORINGAPPROVEDCOIL ASSEMBLYOR

Strany 19 - Formed end of

26UPFLOW DOWNFLOW HORIZONTALYESNONOYESYESYESNO120°MINYES120°MINYES120°MIN90°90°PERFORATEDDISCHARGE DUCTFLANGEA10493Fig. 21 -- Duct Flanges1 3 / 4 ″1

Strany 20 - INSTALLATION

27ANY COMBINATION OF 1, 2, OR 3 PERMITTED.A11036Fig. 25 -- Upflow Return Air Configurations and RestrictionsA11037Fig. 26 -- Downflow Return Air Confi

Strany 21 - Horizontal Installation

282-IN.(51 mm)ROLLOUT PROTECTION REQUIREDInstall 12” x 22” (305 x 559 mm) sheetmetal in front of burner compartmentarea.30 IN. (762 mm)MIN. WORK AREAC

Strany 22 - Filter and Return Duct Sizing

29AIR DUCTSMany states, provinces and localities are considering or haveimplemented standards and/or restrictions on duct sizingpractices, ductwork le

Strany 23

3SAFETY CONSIDERATIONSFIRE, EXPLOSION, ELECTRICAL SHOCK, ANDCARBON MONOXIDE POISONING HAZARDFailure to follow this warning could result in dangerousop

Strany 24 - (FIELD SUPPLIED)

30Table 9 – Air Delivery -- CFM (With Filter)UNITSIZERETURN-AIRCONNECTIONSPEEDTAPS2EXTERNAL STATIC PRESSURE (IN.W.C.)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0

Strany 25

31GAS PIPINGFIRE OR EXPLOSION HAZARDFailure to follow this warning could result in personalinjury, death, and/or property damage.Never purge a gas lin

Strany 26 - UPFLOW DOWNFLOW HORIZONTAL

32Table 10 – Maximum Capacity of PipeNOMINALIRON PIPESIZEIN. (MM)LENGTH OF PIPE --- FT (M)10(3.0)20(6.0)30(9.1)40(12.1)50(15.2)1/2 (13) 175 120 97 82

Strany 27 - ANY MODEL

33J--Box InstallationFIRE OR ELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury, death, or property damage.If field-

Strany 28 - (SEE VENTING SECTION)

34alternate power supply must generate the same voltage, phase, andfrequency (Hz) as shown in Table 11 or the furnace rating plate.Power from an alter

Strany 29 - AIR DUCTS

3524 V Coil To Humidifier Leads To Com/24V Screw Terminal on Thermostat Strip To HUM Terminal On Furnace Control Board To Humidifier Leads A11157Fig.

Strany 30

36BLWNUETRALSTATUS CODE LEDSEC-2 SEC-1EAC-2 L2FUSE 3-AMP0.5 AMP@24VACHUMTEST/TWIN G Com W Y R24V120 18090 150BLOWER OF

Strany 31 - GAS PIPING

37VENTINGNOTE: Planning for the venting system should be done in conjunction with planning for the ductwork, drainage, and furnace accessories,such as

Strany 32 - ELECTRICAL CONNECTIONS

38CARBON MONOXIDE POISONING HAZARDFailure to follow the steps outlined below for each applianceconnected to the venting system being placed into opera

Strany 33 - Alternate Power Supplies

39Table 12 – Vent Termination Kit for Direct Vent (2--pipe)SystemsDIRECT VENT(2---PIPE)TERMINATION KITTERMINATIONSYSTEMDIAMETER OFCOMBUSTION AIRAND VE

Strany 34

413. These furnaces SHALL NOT be installed directly on carpet-ing, combustible tile, or any other combustible material oth-er than wood flooring. In d

Strany 35

40RECOMMENDED SUPPORT FORVENT TERMINATIONSIt is recommended that sidewall vent terminations in excess of24 inches (0.6 M) or rooftop terminations in e

Strany 36

41Optional Combustion Air Inlet Moisture TrapAs an option to prevent moisture from trickling into the furnacevestibule, a trap can be installed in the

Strany 37

42NOTE: Pipe length (ft. / M) specified for maximum pipe lengthslocated in unconditioned spaces cannot exceed total allowable pipelength as calculated

Strany 38 - Venting Systems

4311. Seal around the combustion air pipe with silicone or foiltape. SILICONE SEALERS MAY NOT BE APPRO-PRIATE FOR POLYPROPYLENE VENT SYSTEMS.SEE POLYP

Strany 39 - Locating the Vent Termination

44RECOMMENDED SUPPORT FOR VENTTERMINATIONSIt is recommended that rooftop vent terminations in excess of36 inches (1 M) in vertical length be supported

Strany 40 - Ventilated Combustion Air

45Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)ASTM SPECIFICATION(MARKED ON MATERIAL)MATERIAL

Strany 41 - Guidelines

46Table 14 – Maximum Allowable Exposed Vent Lengths Insulation Table -- Ft. / MMaximum Length of Uninsulated and Insulated Vent Pipe-Ft (M)Single Stag

Strany 42 - Configure the Furnace

47Table 15 – Maximum Equivalent Vent Length -- Ft. (M)0 to 4500 Ft. (0 to 1370 M) AltitudeNOTE: Maximum Equivalent Vent Length (MEVL) includes standar

Strany 43 - Roof Terminations

48Venting System Length CalculationsThe Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting syst

Strany 44

49Table 17 – Maximum Equivalent Vent Length -- Ft. (M)4501 to 10,000 Ft. (0 to 1370 M) AltitudeNOTE: Maximum Equivalent Vent Length (MEVL) includes st

Strany 45

51. Disconnect all power to the furnace. Multiple disconnectsmay be required. DO NOT TOUCH THE CONTROLOR ANY WIRE CONNECTED TO THE CONTROLPRIOR TO DIS

Strany 46

50Attach gaskets to vent pipe andcombustion air adapters.Vent Coupling and AdapterA11314Fig. 37 -- Vent Coupling and Adapter with GasketsPSC INDUCER A

Strany 47

5112346755Rotate vent elbow torequired position.Any other unusedknockout may be usedfor combustion airconnection.&A1130912345675Rotate vent elbow

Strany 48 - Example 2

52Attach vent pipe adapter with gasket to furnace casing.Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.S

Strany 49

53HORIZONTAL LEFT - RIGHT VENT CONFIGURATION**Requires Accessory Internal Vent Kit See Product Data for Current Kit Number HORIZONTAL LEFT -VERTICAL V

Strany 50 - Vent Coupling and Adapter

54HORIZONTAL RIGHT - VERTICAL VENT CONFIGURATIONHORIZONTAL RIGHT - LEFT VENT CONFIGURATION**Requires Internal Vent Kit See Product Data for Current Ki

Strany 51

55VENT PIPE FLUSH SHOWING COUPLINGVENT PIPE FLUSH WITH ADAPTERVENT PIPE ADAPTER WITH GASKETINSTALLED ON FURNACE VENTPIPE IS CUT FLUSH WITH TOP OFADAPT

Strany 52 - Downflow Vertical

56VVA12326NOTE: The following is based upon National codes for gas appliances and is provided as a reference.Refer to local codes which may supersede

Strany 53 - RIGHT VENT CONFIGURATION*

57VVA12325NOTE: The following is based upon National codes for gas appliances and is provided as a reference.Refer to local codes which may supersede

Strany 54

58AA090AVertical separation betweencombustion air and vent8 ¾ in. (222mm) or 3 in.(76mm)6¾ in. (172mm) or 2in. (51mm)Maintain 12 in. (305mm)min. Clear

Strany 55 - VENT PIPE FLUSH WITH ADAPTER

59OPTIONAL TERMINATIONBRACKET FOR 2-PIPETERMINATIONS12-IN. (305 MM)ABOVE ANTICIPATED SNOW LEVEL12-IN.(305 MM)12 IN. (305 MM) SEPARATIONBETWEEN BOTTOM

Strany 56

66 15/16[176.1] 3[76.2]3[76.2]6 11/16[170.1]23 5/16[592.9]25 1/8[638.7]26 3/8[670.0] 26 11/16[678.1]21[534.0]26 5/16[668.8]17 5/16[439.2]16 9/16[420.9

Strany 57

603” (76 mm)12” (305 mm) Pipe hangarVentilated Combustion Airintake termination in crawlspaceVentilated CombustionAir intake pipeCRAWL SPACEATTIChighe

Strany 58 - Roof Termination (Preferred)

61EXAMPLE FORUPFLOW INSTALLATIONS.MAY BE APPLIED TOOTHER CONFIGURATIONS.A12220Fig. 51 -- Sample Inlet Air Pipe Connection forPolypropylene Venting Sys

Strany 59 - (ELBOW PARALLEL TO WALL)

62START--UP, ADJUSTMENT, AND SAFETYCHECKGeneral1. Furnace must have a 115-v power supply properly connec-ted and grounded.NOTE: Proper polarity must b

Strany 60

63The NATURAL GAS manifold pressure adjustments in Table21 compensate for BOTH altitude AND gas heating value.DO NOT apply an additional de--rate fact

Strany 61 - Polypropylene Venting Systems

64FIRE HAZARDFailure to follow this warning could result in personalinjury, death, and/or property damage.Reinstall manifold pressure tap plug in gas

Strany 62 - Adjustments

65Check Safety ControlsThe flame sensor, gas valve, and pressure switch were all checkedin the Start--up procedure section as part of normal operation

Strany 63

66338309-201 Rev. EA11602Fig. 56 -- Service Label Information59SC2A

Strany 64 - Adjust Cooling Airflow

67Table 20 – Gas Rate (CU ft./hr)SECONDSFOR 1 REVOLUTIONSIZE OF TEST DIALSECONDSFOR 1 REVOLUTIONSIZE OF TEST DIAL1CuFt. 2CuFt. 5CuFt. 1CuFt. 2CuFt. 5C

Strany 65

68Table 21 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input RateSAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEATVALUE0.580.600.620.64AT ALTITUDE Or

Strany 66 - 338309-201 Rev. E

69Table 21 -- Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Cont.)SAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEATVALUE0.580.600.620.64AT AL

Strany 67

7THE BLOWER IS LOCATEDTO THE RIGHT OF THEBURNER SECTION, ANDCONDITIONED AIR ISDISCHARGED TO THE LEFT.THE BLOWER ISLOCATED BELOW THEBURNER SECTION, AND

Strany 68 - SINGLE-STAGE FURNACE

70SERVICE AND MAINTENANCEPROCEDURESFIRE, INJURY OR DEATH HAZARDFailure to follow this warning could result in personalinjury, death and/or property da

Strany 69

71Component Self-TestNOTE: The furnace control component test allows allcomponents to run for a short time; except the gas valve andhumidifier termina

Strany 70 - PROCEDURES

722. Check blower motor and wheel for cleanliness each heatingand cooling season. Clean as necessary.3. Check electrical connections for tightness and

Strany 71 - Care and Maintenance

7313. Reinstall blower assembly in furnace.14. Reinstall 2 screws securing blower assembly to blowerdeck.15. Reconnect blower leads to furnace control

Strany 72

74FIRE OR EXPLOSION HAZARDFailure to follow this warning could result in personalinjury, death, and/or property damage.Never purge a gas line into a c

Strany 73

759. Turn gas on at electric switch on gas valve and at externalshut-off or meter10. Turn power on at external disconnect, fuse or circuit break-er.11

Strany 74 - Servicing Hot Surface Igniter

76reach 32_F(0_C) or lower unless winterized. Follow theseprocedures to winterize your furnace:UNIT COMPONENT DAMAGE HAZARDFailure to follow this caut

Strany 75 - Cleaning Heat Exchangers

77SET SCREWMOTOR WHEEL HUBMOTOR SHAFT FLATSCREWMOTOR ARMGROMMETSCREW LOCATIONBLOWER HSG ASSYBRACKETBRACKETENGAGEMENTSEE DETAIL ACAPACITOROR POWER CHOK

Strany 76 - Manifold

78FLAME SENSOR(BELOW BURNER)FLAME ROLLOUTSWITCHBRACKET, IGNITERIGNITERBURNER SUPT. ASSYBURNER ASSYA11403Fig. 63 -- Burner Assembly59SC2A

Strany 77 - Fig. 62 -- Blower Assembly

79SEQUENCE OF OPERATIONNOTE: Furnace control must be grounded for proper operation orcontrol will lock out. Control is grounded through green/yellowwi

Strany 78 - Fig. 63 -- Burner Assembly

8LOCATIONPERSONAL INJURY AND/OR PROPERTYDAMAGE HAZARDImproper use or installation of this furnace may result inpremature furnace component failure. Th

Strany 79 - SEQUENCE OF OPERATION

80Is LED status light on? Is there 24V at SEC-1 and SEC-2? Is there 115V at L1 and L2? Replace furnace control. Is door switch closed? Replace tr

Strany 80 - Troubleshooting Guide

81 11 NO PREVIOUS CODE – Stored codes are erased after 72 hours. Run system through a heating or cooling cycle to check system. 12 BLOWER ON AFTER

Strany 81 - Troubleshooting Guide (Cont)

82338309-201 Rev. EA11603Fig. 65 -- Wiring Diagram59SC2A

Strany 82 - Fig. 65 -- Wiring Diagram

83PARTS REPLACEMENT INFORMATION GUIDECasing GroupBlower doorBottom plateControl doorDoor knob assemblyTop filler plateElectrical Group3--Amp fuseCircu

Strany 83

84Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 . Edition Date: 06/12Manufacturer reserves the right to change, at any ti

Strany 84 - Replaces: 59SC2A---01SI

9FIRE HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.Do not install the furnace on its back or hang

Komentáře k této Příručce

Žádné komentáře